General features:
The panel PAN1-PLUS is a device conceived for acoustic and optical signaling of fires.
All materials utilized to produce it comply to fire system requirements and the housing is built with fireproof
materials.
The alarm device has to be installed by qualified personnel only, respecting all installation norms and
adequate distances and highness to get the best optical and acoustic performances.
Category
Coverage volume
•
Max Current absorption
•
Category
Coverage volume
•
Max Current absorption
•
Nominal Voltage supply
Max Power absorption
Max current absorption for sound
Flash - Strobo frequency
Main sound frequency (average)
Main sound pattern
Max level SPL @1 m
Available Patterns
Operating temperature
Command from the control panel
Enclosure protection degree
Size (WxHxD)
Weight
Standards
Installation and user Manual
Fire alarm devices - Visual and acoustic alarm device
PAN1-PLUS
S-310.1-PAN1P-ENG
PAN1-PLUS
Visual and acoustic fire alarm device
TECHNICAL DATA
W-4,5-10, Wall mounted device (DIP7 OFF)
standard flash power 4,5x10x11 m (HxWxD)
100mA average /140mA peak @ Vdc=24V
W-4-9, Wall mounted device (DIP7 ON)
reduced flash power 4x9x9 m (HxWxD)
70mA average / 90mA peak @ Vdc=24V
24Vdc (from 20Vdc to 30Vdc)
2.4W (DIP7 OFF), 1.7W (DIP7 ON),
20mA +/-5mA
0.6Hz
Sound 1 983 Hz
Sound 1 Pulsed at 1.2 Hz
See Diagram 1
4 available patterns: 1 modulated, 1 pulsed, 1 bitonal,1
continuous
From -10 °C to +55°C
Polarity inversion
IP21C (Type A, for indoor use)
307 x 117 x 55 mm
539 gr
EN54-3:2001 + A1:2002 + A2:2006,
EN54-23:2010
Rev. A.1
02/2018