General features:
The panel PAN1-PLUS is a device conceived for acoustic and optical signaling of fires.
All materials utilized to produce it comply to fire system requirements and the housing is built with fireproof
materials.
The alarm device has to be installed by qualified personnel only, respecting all installation norms and
adequate distances and highness to get the best optical and acoustic performances.
Category
Coverage volume
Max Current absorption
Category
Coverage volume
Max Current absorption
Nominal Voltage supply
Max Power absorption
Max current absorption for sound
Flash - Strobo frequency
Main sound frequency (average)
Main sound pattern
Max level SPL @1 m
Available Patterns
Operating temperature
Command from the control panel
Enclosure protection degree
Size (WxHxD)
Weight
Standards
Installation and user Manual
Fire alarm devices - Visual and acoustic alarm device
PAN1-PLUS
S-310.1-PAN1P-ENG
PAN1-PLUS
Visual and acoustic fire alarm device
TECHNICAL DATA
W-4,5-10, Wall mounted device (DIP7 OFF)
standard flash power 4,5x10x11 m (HxWxD)
100mA average /140mA peak @ Vdc=24V
W-4-9, Wall mounted device (DIP7 ON)
reduced flash power 4x9x9 m (HxWxD)
70mA average / 90mA peak @ Vdc=24V
24Vdc (from 20Vdc to 30Vdc)
2.4W (DIP7 OFF), 1.7W (DIP7 ON),
20mA +/-5mA
0.6Hz
Sound 1 983 Hz
Sound 1 Pulsed at 1.2 Hz
See Diagram 1
4 available patterns: 1 modulated, 1 pulsed, 1 bitonal,1
continuous
From -10 °C to +55°C
Polarity inversion
IP21C (Type A, for indoor use)
307 x 117 x 55 mm
539 gr
EN54-3:2001 + A1:2002 + A2:2006,
EN54-23:2010
Rev. A.1
02/2018

Advertisement

loading

Summary of Contents for Honeywell NOTIFIER PAN1-PLUS

  • Page 1 S-310.1-PAN1P-ENG Rev. A.1 02/2018 PAN1-PLUS Visual and acoustic fire alarm device Installation and user Manual Fire alarm devices - Visual and acoustic alarm device PAN1-PLUS General features: The panel PAN1-PLUS is a device conceived for acoustic and optical signaling of fires. All materials utilized to produce it comply to fire system requirements and the housing is built with fireproof materials.
  • Page 2 Diagram 1 (Sound power distribution): RIGHT Sound S2 – DIP - 5 OFF 6 OFF 100dB 99dBA 101dB - Sound S3 LEFT DOWN DIP 5OFF 6OFF 101dB DIP 5OFF 6FF 101dB DIP 3OFF 4OFF DIP 3ON 4OFF DIP 3OFF 4ON DIP 3ON 4ON DIP 3OFF 4OFF DIP 3ON 4OFF...
  • Page 3 DIP 5OFF 6ON 94dB DIP 5OFF 6ON 94dB DIP 3OFF 4OFF DIP 3ON 4OFF DIP 3OFF 4ON DIP 3ON 4ON DIP 3OFF 4OFF DIP 3ON 4OFF DIP 3OFF 4ON DIP 3ON 4ON min dB(A) @1m min dB(A) @1m min dB(A) @1m min dB(A) @1m min dB(A) @1m min dB(A) @1m...
  • Page 4: Dip Switch

    DIP switch 5-6 Sound Level at 1 m 101 dB OFF - OFF (Default) ON - OFF 97 dB OFF - ON 94 dB ON - ON Sound disabled (NOT COMPLIANT TO EN54-3) Selection of flash power DIP switch 7 Flash pulse power Coverage Current absorption...
  • Page 5 1293 Notifier s.r.l. Via A: Grandi, 22, 20097 S. Donato Milanese (MI) Italy DoP 1293 - CPR - 0597 EN54-3 EN54-23 PAN1-PLUS FIRE ALARM DEVICES – VISUAL AND ACOUSTIC ALARM DEVICE Intended for use in fire detection and fire alarm systems in and around buildings TYPE A: for indoor use Other technical data: see supplier’s technical dossier.