Download Print this page

Honeywell 027966 Brief Instructions page 4

Configuration tool usb

Advertisement

Available languages

Available languages

2
5.2.2
luminAXS reader mifare
These readers have RS-485 and Clock/Data interfaces as
standard.
Note
the
special
parameterization purposes.
5.2.3
LEGIC reader "Insertic" RS-485
(all types incl. Insertic Touch and Feller)
When used on an IDS, it may be necessary to change the LEGIC
operating mode from LEGIC Advant to LEGIC prime.
LEGIC reader Insertic Touch
8
7
6
5
4
3
2
1
Reader Insertic
Reader Insertic-50
Pin no. RS-485
ST1/1
intern belegt
ST1/2
intern belegt
ST1/3
B
ST1/4
A
ST1/5
intern belegt
ST1/6
0 V
ST1/7
+U_b
Honeywell Security and Fire
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de
pin
assignment
required
Wiegand
RS485
RD
1
+UB
1
BU
2
0V
2
YE
3
A
3
WH
4
4
B
BK
5
Syn.
5
GN
6
LED green
BN
7
LED yellow
PK
LED red
8
Free Pins:
- Pins 1 – 4 Wiegand connection
- Pin 5 RS-485 connection
Wiegand
RS485
+UB
0V
A
B
free
LEGIC Advant reader Feller
Pin no. RS-485
6
A
7
B
8
+U_b
9
0 V
P30739-36-002-01
2017-11-16
© 2017 Novar GmbH
6.
Start-up reader
Apply operational voltage.
Start the IQ DeviceInstaller.
for
The green LED on the configuration tool is
controlled
differently
type:
luminAXS reader proX:
The LED flashes:
The LED lights up:
luminAXS reader mifare:
The LED flashes rapidly:
The LED flashes slowly:
LEGIC reader "Insertic":
The LED is always "OFF".
7.
Technical Data
Rated operating voltage
Operating voltage range
Current consumption:
-
in stand by mode
-
with reader
Interfaces
Protection category as per EN 60529 IP40
Environmental class as per VdS
Operating temperature range
Storage temperature range
Dimensions (W x H x D)
Colour
Brief Instructions configuration tool USB
depending on the reader
There is no data
carrier in the
reading field.
Now place any
proX data carrier in the
reading field.
The data carrier is recognized and
evaluated.
There is no data carrier in the reading
field.
Now place any mifare data carrier in the
reading field.
The data carrier is recognized and
evaluated.
12 V DC
9 V to 15 V DC
< 5.0 mA
max. 180 mA
(Lighting ring with full brightness)
RS-485 with modulbus protocol
Clock/Data
II
+5 °C to +40 °C
-25 °C to +70 °C
109 x 85 x 30 mm
traffic white (similar to RAL 9016)