Set-Reset With Memory Function Block (Sm); Controllable Gate Function Block (Gt) - ABB REL 501-C1 2.5 Technical Reference Manual

Line distance protection terminal
Table of Contents

Advertisement

6.11
6.12
50
Configurable logic blocks (CL1)
Table 55:
Output signals for the SR (SRnn-) function block
Signal
OUT
NOUT

Set-reset with memory function block (SM)

The Set-Reset function SM is a flip-flop with memory that can set or reset an output from two
inputs respectively. Each SM function block has two outputs, where one is inverted. The mem-
ory setting controls if the flip-flop after a power interruption will return the state it had before or
if it will be reset.
SM01-
SRM
SET
OUT
RESET
NOUT
xx00000382.vsd
Table 56:
Input signals for the SRM (SMnn-) function block
Signal
SET
RESET
Path in local HMI: ServiceReport/Functions/SRWithMem1/FuncOutputs
Table 57:
Output signals for the SRM (SMnn-) function block
Signal
OUT
NOUT
Path in local HMI: Settings/Function/Groupn/SRWithMem1/SRMem01/MemoryFunct
Table 58:
Setting parameters for the SRM (SMnn-) function
Parameter
Range
Memory
Off/On

Controllable gate function block (GT)

The GT function block is used for controlling if a signal should be able to pass from the input to
the output or not depending on a setting.
Description
Output from SR flip-flop
Inverted output from SR flip-flop
Description
Input to SRM flip-flop
Input to SRM flip-flop
Description
Output from SRM flip-flop
Inverted output from SRM flip-flop
Default
Unit
Description
Off
-
Operating mode of the memory function
Chapter 3
Common functions

Advertisement