System Operation
Operating
Occurs When
Mode
Supervisory
The system detects a
supervisory condition.
The system detects a
supervisory condition
with a CO detector.
Trouble
A system trouble
condition occurs.
A trouble condition with a
CO detector
Pre-alarm
A single detector trips in
a 2-Count zone. (2-Count
means two detectors
must trip before an alarm
is reported.)
98
System Behavior
The communicator seizes control of the phone line and
calls the central station.
The onboard annunciator sounds a loud, pulsing beep in
the sequence one second on, one second off.
The SUPERVISORY LED flashes.
The LCD displays a screen similar to this one.
FIRE: SUPERVISORY
Supervisory Sw
SBUS_97 MODULE_2
1 of 1
Press the right arrow key or Info to display the location
macro, date/time stamp, and site/panel, if applicable.
Site 1
CO: SUPR
[Press for status]
Press the down arrow key to view the type and location of
the Supervisory event. The message will alternate with
the time/date display.
The communicator seizes control of the phone line and
calls the central station.
The on-board annunciator sounds a loud, pulsing beep in
the sequence one second on, nine seconds off.
The SYSTEM TROUBLE LED flashes.
The LCD displays a screen similar to this one.
FIRE: TROUBLE
1 of 1
Pressing the right arrow key or Info will display the
location macro, date/time stamp, and site/panel, if
applicable.
CO: TROUBLE
1 of 1
Pressing the right arrow key or Info will display the
location macro, date/time stamp, and site/panel, if
applicable.
The touchpad piezo beeps.
The LCD displays a screen similar to this one.
FIRE: PREALARM
Det-Photo
SBUS_97 SENSOR_33
1 of 1
Pressing the right arrow key or Info will display the
location macro, date/time stamp, and site/panel, if
applicable.
Table 9.4 Panel Operating Modes (Continued)
Press the down arrow key to view the supervisory
condition. A screen similar to this one displays.
SUPERVSY: MAN_PULL
MODULE_33 POINT_2
[Z002] [M33]
Press SILENCE and enter an Access Code (or
Info>
activate the key) to silence the annunciator.
Once the supervisory condition has been
corrected, the system will restore automatically.
Press the down arrow key to view the trouble. A
screen similar to this one displays.
Pressing the right arrow key or Info will display the
location macro, date/time stamp, and site/panel, if
applicable.
Info>
Press SILENCE and enter an Access Code (or
activate the key) to silence the annunciator.
Once the trouble condition has been fixed, the
system will restore itself automatically.
Info>
Press the down arrow key to view the pre-alarm. A
screen similar to this one displays.
PREALARM:SMOKE-PHOT
MODULE_33 POINT_2
[Z002] [M33]
Info>
All system operations are available in this mode.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Panel Operating Modes
In This Mode You Can
1 of 1
showing 1 of 1 event
FIRE: TROUBLE
Waterflow SW
SBUS_97 MODULE_1
1 of 1
Info>
1 of 1
showing 1 of 1 event
device
type
device
type

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents