Honeywell SILENT KNIGHT 6700 Manual page 21

Addressable fire alarm control panel
Table of Contents

Advertisement

Calculating Current Draw and Standby Battery
5865-3 LED Annunciator Module
5880 LED I/O Module
5883 Relay Interface
Network Cards
SK-NIC Network Interface Card
SK-FML Fiber Optic Multi Mode
SK-FSL Fiber Optic Single Mode
Wireless Modules
WSK-WGI Wireless Gateway
A
Total System Current
Auxiliary Devices
IPDACT-2 IP Communicator
IPDACT-2UD IP Communicator
CELL-MOD/CELL-CAB-SK
HWF2-COM Series
B
Auxiliary Devices Current
Notification Devices
5495/5499 Power Supply
C
Notification Appliances Current
D
Total current ratings of all devices in system (line A + line B + C)
E
Total current ratings converted to amperes (line D x 0.001):
F
Number of standby hours
G
Multiply lines E and F.
H
Alarm sounding period in hours. (For example, 5 minutes = 0.0833 hours)
I
Multiply lines E and H.
J
Add lines G and I.
Multiply by the Derating Factor
Total ampere hours required
1
The FACP can only support 5 devices with LEDs on. The current draw has been added to the panels alarm current.
2
Total does not include isolator devices or accessory bases
3
If using 24 VDC aux power only. No standby or alarm current is needed for battery calculation if using 24 VAC, 120 VAC, or 240 VAC.
4
Maximum SBUS address capacity is determined by the amount of SBUS bandwidth consumed by each SBUS module. Refer to
Section 4.6.1 and for SBUS limitations.
5
If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that
time. However, during normal operation, door holders draw current and must be included in the 1.0A total current that can be drawn from
the panel.
6
Use next size battery with capacity greater than required.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Device
# of Devices
5
Refer to devices manual for current rating
Refer to device manual for current rating
6
Table 3.3 Current Calculation Worksheet for SD Devices (Continued)
Current per Device
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm: (22 mA/relay)
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Max current using ext supply
Max current SLC Power
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Alarm/Standby:
Alarm/Standby:
Standby:
Alarm:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Prerequisites for Installation
Standby
Alarm Current
Current
35 mA
mA
145 mA
35 mA
mA
200 mA
0 mA
mA
220 mA
21 mA
mA
53 mA
mA
79 mA
mA
40 mA
mA
24 mA
mA
93 mA
mA
136 mA
98 mA
mA
155 mA
55 mA
mA
100 mA
210 mA
mA
290 mA
mA
mA
mA
mA
75 mA
205 mA
mA
mA
mA
mA
A
H
AH
AH
1.25
AH
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
H
AH
21