Download Print this page

Honeywell FIRE-LITE ALARMS ES-50X Series Manual page 3

Intelligent addressable fire alarm control panels
Hide thumbs Also See for FIRE-LITE ALARMS ES-50X Series:

Advertisement

H365(A)-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed
and CLIP mode.
H365R(A): Low-profile, intelligent, rate-of-rise thermal sensor. Lite-
Speed only.
H365R(A)-IV: Low-profile, intelligent, rate-of-rise thermal sensor.
Ivory. LiteSpeed and CLIP mode.
H365HT(A): Low-profile intelligent 190°F/88°C fixed thermal sensor.
LiteSpeed only.
H365HT(A)-IV: Low-profile intelligent 190°F/88°C fixed thermal sen-
sor. Ivory. LiteSpeed and CLIP mode.
D365PL(A): Low-flow non-relay duct-detector housing; includes
SD365R(A).
Legacy Devices
CP355(A)
Addressable, intelligent smoke detector that incorporates an
ionization sensing chamber.
SD355(A): Addressable low-profile photoelectric smoke detector.
SD355T(A): Addressable low-profile photoelectric smoke detector
with thermal sensor.
SD355R(A): Remote test capable addressable photoelectric smoke
detector for use with DNR(W)(A) duct detector housing.
SD355CO: Addressable, low-profile device that provides fire, heat,
and carbon monoxide (CO) detection.
H355(A): Fast-response, low-profile heat detector.
H355R(A): Fast-response, low-profile heat detector with rate-of-rise
option.
H355HT(A): Fast-response, low-profile heat detector that activates at
190°F/88°C.
AD355(A): Low-profile, intelligent, "Adapt" multi-sensor detector
(B350LP base included).
B200S(A)(-WH)(-IV): Programmable, addressable sounder base.
B200SR(A)(-WH)(-IV): Addressable sounder base.
B200S-LF(-WH)(-IV): Programmable, addressable sounder base, low-
frequency.
B200SR-LF(-WH)(-IV): Addressable sounder base, low-frequency.
BEAM355: Intelligent beam smoke detector.
BEAM355S: Intelligent beam smoke detector with integral sensitivity
test.
D355PL(A): InnovairFlex low-flow non-relay duct-detector housing;
includes SD355R(A).
DNR(A): InnovairFlex™ low-flow non-relay duct-detector housing.
(Order SD355R(A)/SD365R(A) separately.)
DNRW: InnovairFlex low-flow non-relay duct-detector housing, with
NEMA-4 rating. Watertight. (Order SD355R(A)/SD365R(A) sepa-
rately.)
Addressable Modules
MMF-300(A): Addressable Monitor Module for one zone of normally-
open dry-contact initiating devices. Mounts in standard 4.0" (10.16
cm.) box. Includes plastic cover plate and end-of-line resistor. Module
may be configured for either a Class B or Class A IDC.
MDF-300(A): Dual Monitor Module. Same as MMF-300(A) except it
provides two Class B-only IDCs.
MMF-301(A): Miniature version of MMF-300(A). Excludes LED and
Class A option. Connects with wire pigtails. May mount in device back-
box.
MMF-302(A): Similar to MMF-300(A). Addressable Monitor Module for
one zone of conventional two-wire detectors. Requires resettable 24
VDC power. Refer to the Device Compatibility Document for listed
compatible devices and quantity limitation.
CMF-300(A): Addressable Control Module for one Class B or Class A
zone of supervised polarized Notification Appliances. Mounts directly
to a 4.0" (10.16 cm.) electrical box. NAC option requires external 24
VDC to power notification appliances.
CRF-300(A): Addressable relay module containing two isolated sets
of Form-C contacts, which operate as a DPDT switch. Mounts directly
to a 4.0" (10.16 cm.) box, surface mount using the SMB500.
BG-12LX: Addressable manual pull station with interface module
mounted inside.
I300(A): This module isolates the SLC (DCL) loop from short circuit
conditions (required for Class A or Class X operation).
ISO-6(A): Six-fault isolator module. Mount one or two modules in a
BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chas-
sis in a BB-6F cabinet.
SMB500: Used to mount all modules except MMF-301 and M301.
MMF-300-10(A): Ten-input monitor module. Mount one or two mod-
ules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-
6 chassis in a BB-6F cabinet.
MMF-302-6(A): Six-zone interface module. Mount one or two modules
in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6
chassis in a BB-6F cabinet.
CMF-300-6(A): Six-circuit supervised control module. Mount one or
two modules in a BB-2F cabinet (optional). Mount up to six modules
on a CHS-6 chassis in a BB-6F cabinet.
CRF-300-6(A): Six-relay control module (Form-C relays). Mount one
or two modules in a BB-2F cabinet (optional). Mount up to six modules
on a CHS-6 chassis in a BB-6F cabinet.
SWIFT Wireless Devices
W-GATE(A): LiteSpeed Wireless Gateway
W-SD355(A): LiteSpeed intelligent, wireless photo detector.
W-H355R(A): LiteSpeed intelligent wireless rate of rise (135°) heat
detector.
W-SD355T(A): intelligent wireless photo/heat detector.
W-H355(A): LiteSpeed intelligent wireless fixed-temperature (135°)
heat detector.
W-MMF(A): LiteSpeed Intelligent wireless monitor module.
W-CRF(A): LiteSpeed Intelligent wireless relay module.
W-BG12LX(A): LiteSpeed Intelligent wireless pull station.
WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: LiteSpeed Intelligent AV
bases.
W-USB: Wireless USB radio/antenna dongle that plugs into the USB
port of a PC running SWIFT Tools.
SWIFT Tools: Programming and diagnostic utility for the Wireless
Gateway and devices. Available for download from www.firelite.com.
NOTE: For more information on Compatible Addressable Devices for use
with the ES-50X, see the following data sheets (document numbers):
SD365 Series (DF-61010), H365 Series (DF-61011), AD355 (DF-52386),
BG-12LX (DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-52374),
CMF/CRF Series (DF-52130), CP355 (DF-52383), H355 Series (DF-
52385), I300 (DF-52389), ISO-6 (DF-60485), MMF-300 Series/MDF-300
(DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), SD355/
SD355T (DF-52384), and SLC Wiring Manual (51309).
NOTE: Legacy 300 Series detection devices such as the CP300/CP350,
SD300(T)/SD350(T) and older modules such as the M300, M301, M302,
C304, and BG-10LX are not compatible with LiteSpeed polling. If the SLC
(DCL) contains one of these devices, polling must be set for standard CLIP
protocol. Please consult factory for further information on previous 300
Series devices.
ADDRESSABLE DEVICE ACCESSORIES
End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm
assembly supervises the MMF-300(A), MDF-300(A), MMF-301(A),
and CMF-300(A) module circuits. The 3.9k ohm assembly supervises
the MMF-302(A) module circuit. These resistors are included with
each module.
Power Supervision Relay: Supervises the power to 4-wire smoke
detectors and notification appliances.
Wiring Requirements
While shielded wire is not required, it is recommended that all SLC/
DCL wiring be twisted-pair to minimize the effects of electrical interfer-
ence. Refer to the panel manual for wiring details.
DF-60953:D • 3/27/2023— Page 3 of 4