BG-12S Manual Pull Station
Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,314,772
Document 50964-2
Description
The BG-12S pull station is a non-coded, single-action manual pull station with pigtail con-
nections and a hex-lock reset feature. It provides Fire•Lite control panels with one normally
open (N/O) alarm initiating input. The BG-12S meets the ADAAG controls and operating
mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum
pull force to activate the pull station. Operating instructions are molded into the pull station
handle along with Braille text.
Ratings
Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12S pull station can be surface mounted to an SB-10 or SB-I/O surface backbox
or semi-flush mounted on a standard single-gang, double-gang or 4" (10.16 cm) square
electrical box. The optional BG-TR trim ring can be used if the BG-12S is to be semi-flush
mounted.
Operation
To activate the single-action pull station, simply pull down the handle. The word 'ACTI-
VATED' appears after the handle is pulled down. This will remain until the pull station is
reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station.
Resetting the Pull Station
1. To reset the BG-12S hex lock pull station, insert the supplied 9/64-inch hex wrench
into the lock until firmly seated and turn counterclockwise 1/4-turn.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
Note: Closing the door automatically resets the switch to the 'Normal' position. Opening
the door will not activate or deactivate the alarm switch.
Wiring
'PIGTAILS'
BLACK IN/OUT (–)
RED IN/OUT (+)
RED
I56-2263-005
BLACK
CAUTION! Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has already been
installed onto an electrical box.
CAUTION!
Install the Fire•Lite BG-12S pull station in accordance with these instructions,
applicable NFPA standards, national and local Fire and Electrical codes and the requirements
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to an object, the
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
54 inches (137.16 cm).
BG-12S
Manual Pull Station
Document 50964-2
I56-2263-005

Advertisement

loading

Summary of Contents for Honeywell Fire-Lite Alarms BG-12S

  • Page 1 BG-12S Wiring Manual Pull Station ‘PIGTAILS’ Document 50964-2 I56-2263-005 BLACK IN/OUT (–) RED IN/OUT (+) BG-12S Manual Pull Station Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,314,772 Document 50964-2 I56-2263-005 Description The BG-12S pull station is a non-coded, single-action manual pull station with pigtail con- BLACK nections and a hex-lock reset feature.
  • Page 2 Alambrado CABLES FLEXIBLES NEGRO ENTRADAS/SALIDA (–) ROJO ENTRADA/SALIDA (+) BG-12S Estación Pulsadora Manual ROJO Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,314,772 Documento 50964-2 I56-2263-005 Descripción La estación pulsadora BG-12S es una estación no códificada y de acción manual individual NEGRO con conecciones entrelazadas y una característica de reajuste de una cerradura hexagonal.