Photoelectronic smoke detector with built-in wireless transmitter

Advertisement

Maintenance
NOTE: Before performing maintenance on the detector, notify the
proper authorities and the central station that maintenance is being
performed and the system will be temporarily out of service. Disable
the zone or system undergoing maintenance to prevent any unwanted
alarms, and follow this procedure exactly, referring to Figure 5.
1.
Remove the detector housing from the base by twisting
counter-clockwise.
2.
Remove the battery from the unit.
3.
Wait 20 seconds. (To ensure proper power-down sequence, the
battery must be removed from detector for a minimum of 20
seconds before continuing to the next step.)
4.
Remove the detector cover by turning counter-clockwise.
5.
Vacuum the cover or use canned air to remove any dust or debris.
6.
Remove the top half of the screen/sensing chamber by lifting
straight up (see Figure 5).
7.
Vacuum or use canned air to remove any dust or particles that
are present on all chamber sections.
8.
Replace the top half of the screen/sensing chamber by aligning
the arrow on the screen/sensing chamber with the arrow on the
housing. Press down firmly until the screen/sensing chamber is
fully seated.
9.
Replace the detector cover by placing it over the screen/sensing
chamber and turning it clockwise until it snaps into place.
Specifications
Power Source:
Height:
Diameter:
Weight:
Operating Ambient Temperature Range:
Operating Humidity Range:
Agency Listings:
Please refer to insert for the Limitations of Fire Alarm Systems
FOR WARRANTY INFORMATION AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION INSTRUCTIONS FOR THE
RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED.
This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
Unauthorized changes or modifications could void the user's authority to operate the equipment
HW-500-000
10. Reinstall the battery into the battery compartment noting proper
11. Reinstall the detector and test (see the Testing section).
12. Notify the central station when the system is back in service.
One 3-volt CR123A Lithium Battery (included). (Replace with Duracell DL123A, Sanyo CR123A,
Panasonic CR123A or ADEMCO 466.)
2.3 inches (58 mm)
5.3 inches (135 mm) with mounting base
8.5 oz. (241 g) without battery
32° to 100°F (0° to 38°C)
0% to 95% Relative Humidity
UL 268 – Commercial and Residential Installations
2 Corporate Center Drive, Melville, NY 11747
Copyright © 2008 Honeywell International Inc.
www.honeywell.com/security
orientation. The red and green LEDs will flash once every 5
seconds for approximately 20 seconds until the power-up cycle is
complete.
IMPORTANT: If this procedure is not followed exactly, the
detector may indicate a maintenance trouble after the power-up
sequence is complete. If this happens, remove the battery for 20
seconds and then reinstall.
REMOVABLE
DETECTOR
COVER
DETECTOR HOUSING
Figure 5. Removing Screen/Sensing Chamber
SCREEN/SENSING
CHAMBER
(TOP HALF)
S0111-00
I56-3022-004R