Download Print this page

Honeywell 5806W3 Installation And Setup Manual page 2

Photoelectronic smoke detector with built-in wireless transmitter

Advertisement

Battery Installation and Replacement
To replace the battery:
1.
Remove the detector from its mounting base by twisting the detector
counterclockwise. Remove the battery, and dispose properly.
2.
To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new battery.
3.
Install a new 3-volt CR123A Lithium battery in the battery
compartment. Follow the polarity diagram inside the compartment.
4.
Reinstall the smoke detector onto the mounting base by turning
the detector clockwise.
5.
Test the detector as described in the TESTING SIGNAL
STRENGTH section of this manual. The green LED should blink
about once every 10 seconds to indicate normal operation. If the
battery is not installed correctly, the smoke detector will not
operate and the battery may be damaged. If the detector does not
appear to be sending a signal during any of the tests, check for
correct battery installation and for a fully charged battery.
TEST SWTICH
GREEN LED
RED LED
Figure 1. 5806W3 Wireless Smoke Detector
Programming
The smoke detector must be enrolled in the control panel before it can
operate in the system. The 5806W3 smoke protection zone must be
enrolled as Loop 1 and "Input Type" 3 (supervised RF).
If programmed, this smoke detector is capable of monitoring the
additional condition of Maintenance (transmitted as Loop 2). Tamper
is transmitted as Loop 4, but does not require programming. To take
advantage of the value added feature of Maintenance, you must
program each loop as a separate zone in the 5800 series wireless
compatible panel.
1.
Enter the control's Zone Programming mode.
2.
Enter the zone number to be programmed.
3.
Enter the applicable zone type when prompted. Program
• Loop 1 (Smoke) as a Fire zone (type 9 or 16),
• Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type
19), and
NOTE: Loop 2 High/Low Maintenance is supported only on
commercial control panels such as the Vista-128FBP.
4.
When prompted, enter Input Type 03 (3 on some controls)
– Supervised RF Transmitter.
5.
When prompted for the serial number, transmit from the detector
by activating the tamper switch. To do this, hold the base of the
detector in one hand, and rotate the detector counter-clockwise
on the base until it snaps open. Then return to clockwise position
until the detector snaps into place.
6.
When the serial number is displayed, transmit from the detector
a second time by activating the tamper switch again as described
in Step 5. The current loop number (4) will begin to flash.
7.
Manually change the loop number to the desired loop number for
the zone (according to the application).
8.
When programming for this zone is complete, program other
zones for the transmitter as necessary (except for Tamper Loop
4, which does not require programming).
WARNING: The fire protection zone enrolled must always be
Loop 1. Otherwise, fire annunciations will not be reported by the
control.
9.
Exit Programming mode when programming is complete, and
test the detector. Refer to the Testing Section.
See the control unit's installation instructions for further details.
Mounting
First, determine the best location for the smoke detector, one that
provides a strong wireless transmission path and proper smoke
detection. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED
FROM THE PROPOSED MOUNTING LOCATION BEFORE
PERMANENTLY INSTALLING THE DETECTOR. To check, perform
the test described in the TESTING SIGNAL STRENGTH section of
this manual. Prior to mounting the detector to the mounting base,
you must "enroll" the detector's serial number into the system (see
the PROGRAMMING section). To mount the detector, perform the
following steps:
1.
Once a suitable location has been determined, install the
mounting base on the ceiling or on the wall (if local ordinances
permit). Use the two screws and anchors provided.
S0289-00
2.
Turn the detector in a clockwise direction in the mounting base
until it clicks into place.
3.
Test the detector immediately after completing the installation
(as described in the TESTING section of this manual) and refer
to the control system's instructions for additional information
concerning the use of wireless smoke detectors.
TAMPER RELEASE TAB
Figure 2. Detector Mounting Base
Figure 3. Mount Detector Across Ceiling Panel Support
DO NOT attach the detector to removable ceiling
panels. Attach the detector across panel support as
shown in Figure 3.
- 2 -
DIRECT MOUNT HOLES
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO ACTIVATE
TAMPER RESIST FEATURE)
S0290-00
S0162-01

Advertisement

loading