3.4
Setting as for 1.4
Please note:
For maximum pressure limiters the scale value corresponds to the upper switching point.
4.
Pressure limiters with gold plated contact DWAM...-213, ...-513
Gold plated contacts are used exclusively in the low voltage range in order to keep the transit
resistance at the contacts low.
4.1
Technical Data as for 1.1
Switching capacity
At higher voltages and currents, the gold layer on the contacts will be damaged.
All other data correspond to the basic equipment.
max. 24 V DC
max. 100 mA
min. 5 V DC
min. 2 mA