INSTALLATION AND MAINTENANCE INSTRUCTIONS
MMF-302A Interface Module
SPECIFICATIONS
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC Wiring Resistance:
IDC Supply Voltage (between Terminals T10 and T11)
Regulated DC Voltage:
Ripple Voltage:
Alarm Current:
Standby Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The MMF-302A Interface Module is intended for use in intelligent, two-wire
systems, where the individual address of each module is selected using the
built-in rotary switches. This module allows intelligent panels to interface and
monitor two-wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors back to the
control panel. All two-wire detectors being monitored must be ULC compat-
ible with this module. The MMF-302A has a panel controlled LED indicator
and can be used to replace an M302A module in existing systems. MMF-302A
is capable of handling more than one detector in alarm condition.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Fire•Lite system control panel only (list available from Fire•Lite).
MOUNTING
The MMF-302A mounts directly to 4-inch square electrical boxes. (See
Figure 2.) The box must have a minimum depth of 2.125 inches. Surface
mounted electrical boxes (SMB500) are available from Fire•Lite.
FIGURE 1. CONTROLS AND INDICATORS
15 to 32 VDC
5.1 mA (LED on)
270 µA (LED flashing)
3.9K Ohms
25 Ohms
24 VDC power limited
0.1 Volts RMS maximum
90 mA per module
13 mA Maximum @24 VDC
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Non-condensing
4.5˝ H × 4˝ W × 1.25˝ D (Mounts to a 4˝ square by 2.125˝ deep box.)
SMB500 Electrical Box
C1059-00
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power-limited wiring only.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box supplied by installer. (See Figure 2.)
FIGURE 2. MODULE MOUNTING
1
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
ISOLATED
QUADRANT
C1066-00
I56-3219-002
7/1/2022

Advertisement

loading

Summary of Contents for Honeywell FIRE-LITE ALARMS MMF-302A

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS One FireLite Place MMF-302A Interface Module Northford, CT 06472 Phone: 203.484.7161 SPECIFICATIONS Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.1 mA (LED on) Average Operating Current: 270 µA (LED flashing) EOL Resistance: 3.9K Ohms Maximum IDC Wiring Resistance: 25 Ohms IDC Supply Voltage (between Terminals T10 and T11)