2.3

Wiring

Wiring an IAI controller

This section shows how to wire an IAI controller.
Wiring the power connector
Wire the power connector.
+24V
+24V
0V
1.
Check that the MPI terminal and MPO terminal of the power connector have been short-circuited, and insert the
connector into the IAI controller.
2.
Connect the S1 terminal of the power connector and the +24V terminal of the 24VDC power supply.
The emergency stop state occurs when +24V power supplied to the S1 terminal is cut.
To wire the emergency stop switch, add a dry contact (b contact) to the wired part of the S1 terminal. (24VDC,
10mA or less)
3.
Connect (short-circuit) the S2 terminal and EMG- terminal of the power connector.
4.
Connect the 24V terminal of the power connector and the +24V terminal of the 24VDC power supply.
5.
Connect the 0V terminal of the power connector and the 0V terminal of the 24VDC power supply.
2 PREPARATION
11
2.3 Wiring
File name
PositioningSupportIAI_F.mslm
Emergency
stop switch
BK
S1
S2
MPI
MPO
24V
0V
EMG-
Reference
Page 17 PROGRAMMABLE CONTROLLER
SETTINGS