3. How to Install the Indoor Unit

Recessed Type (XS Type)

3-1. Suspending the Indoor Unit

This unit uses a drain pump. Use a carpenter's level to
check that the unit is level.

3-2. Preparation for Suspending

(1)
Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs.
3-1 and 3-2), by attaching them to the ceiling
support structure, or by any other method that
ensures that the unit will be securely and safely
suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes
in the ceiling.
Table 3-1
Length
Type
XS2432 (PNR-XS2432)
32-9/32 (820)
XS3632, XS4232
43-11/16 (1,110) 40-5/32 (1,020)
(PNR-XS3632)
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 3-3 and Table 3-2) show
the relationship between the positions of the
suspension fitting, the unit, and the panel.
Table 3-2
Length
Type
XS2432 (PNR-XS2432) 5-29/32 (150)
XS3632, XS4232
6-1/2 (165)
(PNR-XS3632)
Unit : inch (mm)
A
B
28-3/4 (730)
Refrigerant tubing joint (narrow tube side)
Refrigerant tubing joint (wide tube side)
Suspension lug
1/2
A
B
7-7/8 (200)
10-1/32 (255) 11-23/32 (298) 4-29/32 (125)
9-1/4 (235)
11-7/32 (285) 12-29/32 (328) 4-29/32 (125)
10
Hole-in-anchor
Hole-in-plug
Concrete
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-1
A
(Ceiling opening)
B
(Suspention bolt pitch)
Fig. 3-2
Fig. 3-3
C
D
S4359249
Insert
0038_T_I
Power line
(conduit size : 1/2)
Control line
Refrigerant
tubing side
Drain hose
side
Unit : inch
1094_X_I
Drain connection
1/2
1095_X_I
Unit: inch (mm)
E
F
6-1/2 (165)
6-1/2 (165)