Honeywell Velociti Series Installation And Maintenance Instructions

Six zone interface module

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
Velociti
Series
®
MMI-6SF Six Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage:
Standby Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum IDC Wiring Resistance:
External Power Supply Voltage:
Ripple Voltage:
IDC (supervised and power limited)
DC Voltage:
Frequency:
Alarm Current:
Standby Current 6 circuits:
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The MMI-6SF Six Zone Interface Module is intended for use in an intelligent
alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(5) 1×4 TERMINAL
(2) 1
/
˝ STAND OFFS
1
4
BLOCKS
(1) LONG POWER SUPPLY JUMPER
(4) MACHINE
(2) NUTS
SCREWS
(6) 3.9k OHM
END OFLINE RESISTORS
15-32VDC
2.3 mA @ 24 V
40 mA (assumes all six LEDs solid on)
32ºF to 120ºF ( 0ºC to 49ºC)
10% to 85% Non-condensing
6.8˝ H x 5.8˝ W x 1.0˝ D
CHS-6 Chassis; MBB-6 Cabinet; MBB-2 Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets
12-18 AWG
25 Ohms
Regulated 24 VDC
0.1 volts RMS maximum
18-28 volts power limited
DC
90mA per circuit
42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28 VDC
(3) SHUNTS
C1053-00
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Gamewell-FCI system control panel (list available from Gamewell-FCI).
A list of compatible two-wire System Sensor Smoke detectors for use with the
MMI-6SF is available on the System Sensor website at www.systemsensor.
com.
COMPONENTS
Following are descriptions of the MMI-6SF mounting frameworks. There are
two mounting options for MMI-6SF modules:
• Up to six MMI-6SF modules can be installed on a CHS-6 in a CAB-3
Series, CAB-4 Series or MBB-6 cabinet
• One or two MMI-6SF modules can be installed in a MBB-2 cabinet
Chassis
The CHS-6 chassis is used to mount MMI-6SF modules in a MBB-6, CAB-3 or
CAB-4 Series cabinet. It accommodates up to six MMI-6SF modules in a single
cabinet row three modules wide and two modules deep.
FIGURE 1. CHS-6 CHASSIS
SELF-THREADING SCREWS
1
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161; Fax: 203.484.7118
www.gamewell-fci.com
MOUNT WITH
TO BACK OF CABINET
I56-2742-009
C0236-01
7/1/2022

Advertisement

loading

Summary of Contents for Honeywell Velociti Series

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS Velociti Series ® 12 Clintonville Road Northford, CT 06472-1653 MMI-6SF Six Zone Interface Module Phone: 203.484.7161; Fax: 203.484.7118 www.gamewell-fci.com SPECIFICATIONS Normal Operating Voltage: 15-32VDC Standby Current: 2.3 mA @ 24 V Alarm Current: 40 mA (assumes all six LEDs solid on) Temperature Range: 32ºF to 120ºF ( 0ºC to 49ºC) Humidity:...
  • Page 2: Installation Steps

    The MBB-2 cabinet has a built-in chassis that will accommodate one or two a chassis. Method one is for installation of a rear module only, when MMI-6SF modules. no module will be installed in front of it. Refer to Figure 5 for instruc- tions.
  • Page 3: Wiring Notes

    FIGURE 6C. INSTALLATION OF MMI-6SF MODULE IN FRONT CHASSIS example, if the base address switch is set to 28, then 30 and 32 will be POSITION automatically assigned to the modules while 29, 31 and 33 are available to be used for other modules on the SLC. For Class A and B operation, DO NOT set the lowest address above 154, as the other modules will be assigned to nonexistent addresses.
  • Page 4 FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A To select Class A, remove the two shunts from the “A/B select” positions. To use a common power supply between multiple MMI-6SF modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent MMI-6SF module.
  • Page 5: Fcc Statement

    – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. Velociti , Gamewell-FCI , System Sensor , and Honeywell are registered trademarks of Honeywell International, Inc. ® ® ® ® I56-2742-009...

This manual is also suitable for:

Mmi-6sf