Hitachi Relion 670 Series Product Manual page 78

Line differential protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Line differential protection RED670
Version 2.2
Table 27. Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence, operate
value
Interrupted auxiliary DC voltage
Interruption
interval
0–50 ms
0–∞ s
Restart time
Table 28. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Frequency dependence for distance protection operate value
Harmonic frequency dependence (20% content)
Harmonic frequency dependence for distance protection (10%
content)
Harmonic frequency dependence for high impedance differential
protection (10% content)
Harmonic frequency dependence for overcurrent protection
78
Reference value
Within nominal
range
max. 2%
15% of EL
Full wave rectified
±20% of EL
24-60 V DC ± 20%
90-250 V DC ± 20%
Within nominal range
f
r
f
r
f
r
f
r
2
2
2
2
© 2017 - 2022 Hitachi Energy. All rights reserved
Influence
0.01%/%
0.01%/%
No restart
Correct behaviour at power down
< 300 s
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
nd
rd
th
, 3
and 5
harmonic of f
r
nd
rd
th
, 3
and 5
harmonic of f
r
nd
th
, 3rd and 5
harmonic of f
r
nd
rd
th
, 3
and 5
harmonic of f
r
1MRK 505 379-BEN R
Influence
±1.0%/Hz
±2.0%/Hz
±2.0%
±10.0%
±10.0%
±3.0%
Hitachi Energy

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents