FIGURE 2A. MODULE MOUNTING
WITH BARRIER:
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
FIGURE 3. RELAY MODULE WIRING DIAGRAM:
TO NEXT
DEVICE
RELAY COMMON 2
NORMALLY CLOSED 2
NORMALLY OPEN 2
RELAY COMMON 1
NORMALLY CLOSED 1
MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
Farenhyt™ is a trademark of and Honeywell
®
is a registered trademark of Honeywell International, Inc.
FIGURE 2B:
C1070-00
CONTROL
MODULE
UNUSED
NORMALLY OPEN 1
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier
must be inserted into a 4" × 4" × 2
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer), as shown in
Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is
1
/
" to
3
/
"). Exposed conductor should be secured under the clamping plate
4
8
and should not protrude beyond the terminal block area. Caution: Do not loop
wire under terminals. Break wire run to provide supervision of connections.
NOTE: All references to power limited represent "Power Limited (Class 2)".
WARNING
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
IF ANY WIRING TO TERMINALS 4 – 10 IS NONPOWER
LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500
INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST
BE PLACED OVER THE POWER LIMITED TERMINAL
INFORMATION ON THE NAMEPLATE LABEL.
2
1
/
" junction box, and the control module
8
FROM PANEL OR
PREVIOUS DEVICE
C0946-00
I56-3601-005
©2017 Honeywell. 04-21