Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with Status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index
90
P-GrpC act
91
P-GrpD act
92
ModeREMOTE
HMI
93
Local ON
94
Auto ON
95
Restore ON
96
Simulation ON
97
HotLineTag ON
98
MotorInhibit ON
99
Lockout ON
SIPROTEC Compact, Feeder Protection and Recloser Controller 7SC80, Bus Mapping/Point Lists
C53000-L2040-C353-3, Edition 09.2018
Name
Setting Group C; 0 = Group C is deactivated,
1 = Group C is activated and Groups A, B, D are deactivated.
Setting Group D; 0 = Group D is deactivated,
1 = Group D is activated and Groups A, B, C are deactivated.
Control mode REMOTE; UNLOCKED = 1, LOCKED = 0
Local Mode is active
Auto Mode is active
Restoration Mode is active
Simulation Mode is active
Hot Line Tag is active
Motor Inhibit is active
Lockout is active
Description
Point Lists
2.1 Binary Input Points
Class
1
1
3
3
3
3
3
3
3
3
23