Chapter 6. Diagnostics
Channel
Diagnosis
Error
AlarmType
Type
Channel Diagnosis
Appears/Disappears:
16
Parameterization
Fault
Channel Diagnosis
17
Appears/Disappears:
Power supply fault
Channel Diagnosis
18
Appears/Disappears:
Fuse blown / open
Channel Diagnosis
257
Appears/Disappears
Channel Diagnosis
258
Appears/Disappears
Channel Diagnosis
259
Appears/Disappears
Channel Diagnosis
260
Appears/Disappears
62
Module or
Channel
Cause
Error
Rejected
Configuration The
intelligent module
rejected the
Module
configuration due to
one of the
parameters being
incorrect.
Loss of field power
Module
to module
Channel
Short circuit
Channel
Over range fault
Channel
Under range fault
High-high alarm
Channel value is
Channel
above configured
High High Alarm.
Low-low alarm
Channel value is
Channel
below configured
Low Low Alarm.
PACSystems* RX3i CEP PROFINET Scanner
Fault Text
Recommended Action
Verify the settings of the
module with the module
documentation. The
Module not
module does not support
Configured
all settings allowed by
GSDML in non-GE
Automation & Controls
I/O Controllers.
Verify field power to the
specified module is wired
and energized correctly.
Power supply
fault
Note This does not apply
to the input power on the
RX3i CEP.
There are no corrective
Fuse Blown
actions for this. Try to fix
the IO module hardware.
Correct Wiring
Provide input in
correct range (such
Over Range
as 4-20mA)
Verify output is
within range (remove
shorts)
Correct Wiring
Provide input in
correct range (such
Under Range
as 4-20mA)
Verify output is
within range (remove
shorts)
Bring process value
High-high alarm
below configured High-
high alarm level.
Bring process value
above configured Low-
Low-low alarm
low alarm level.
GFK-2883E