7
EXTENSION POWER SUPPLY MODULE

PERFORMANCE SPECIFICATIONS

This chapter describes the performance specifications of the extension power supply module.
7.1
Performance Specifications
Item
Rated voltage
Voltage fluctuation range
Rated frequency
Allowable instantaneous power failure time
Power fuse
Rush current
Power consumption
24VDC built-in power supply capacity
5VDC built-in power supply
External color
Mass (weight)
*1 The FX5 safety extension module is not subject to the allowable momentary power failure time.
*2 The voltage fluctuation range is included.
*3 When the ambient temperature exceeds 40, use the extension power supply module at the following current values within the derating
range.
Derating chart
For FX5-1PSU-5V
Output current
[mA]
5VDC
1200
800
24VDC
300
200
40
55
Specifications
FX5-1PSU-5V
100 to 240VAC
-15%, +10%
50/60Hz
*1
Operation can be continued upon occurrence of
instantaneous power failure for 10ms or less.
250V, 3.15A Time-lag fuse
25A max. 5ms or less/100VAC
50A max. 5ms or less/200VAC
20W max.
300mA
1200mA
Munsell 0.6B7.6/0.2
Approx. 0.3kg
For FX5-C1PS-5V
Output current
1200
800
625
400
Ambient
temperature
[]
7 EXTENSION POWER SUPPLY MODULE PERFORMANCE SPECIFICATIONS
FX5-C1PS-5V
24VDC
+20%, -15%
Operation can be continued upon occurrence of
instantaneous power failure for 5ms or less.
125V, 3.15A Time-lag fuse
35A max. 0.5ms or less/24VDC
*3
30W
625mA
1200mA
Munsell 0.6B7.6/0.2
Approx. 0.1kg
[mA]
5VDC
24VDC
Ambient
temperature
[]
40
55
7.1 Performance Specifications