Model RA-2000 Installation Instructions
screws.
Figure 4: Attaching Door Assembly to Backbox
Surface Mounting
1. Remove the desired knockout. See Figure 3.
2. To properly mount the backbox, insert a single
screw into the key shaped mounting hole. Do not
tighten all the way. See Figure 5.Place a level on
top of the backbox, with the backbox level insert
the rest of the mounting screws.
key shaped
mounting hole
backbox
mounting holes
Figure 5: Backbox Surface Mount Holes
3. Connect wires from the RA-2000 to the SBUS
connectors on the FACP. See Figure 7.
4. The RA-2000TR or RA-2000GRAYTR ring trim
kits are available for use when surface mounting.
Place the trim ring over the backbox as shown in
Figure 6.
Figure 6: Installing Trim Ring
5. Attach the annunicator/door assembly to the
2
backbox using screws provided (see Figure 4).
6. Replace the electronic assembly in the backbox.
Wiring Connections
Wire the RA-2000 to the FACP as Shown in Figure 7.
Figure 7: SBUS Connections
Installation
1. Ensure power is turned off at the panel.
2. Mount the RA-2000 in the desired location.
3. Connect the RA-2000 to the panel (see Figure
7).
4. Use the DIP switches on the back of the RA-
2000 to assign an ID number. (See FACP
manual).
5. The RA-2000 module must be added to the
system through programming. JumpStart
add the module automatically. Refer to the FACP
manual for more information.