Download Print this page

Honeywell T775B Series Instruction Instructions page 15

Hide thumbs Also See for T775B Series:

Advertisement

1. PROGRAMMING
PROGRAM
RELAY 1
DIFFRNTL
Fig. 29. Program - Differential or Throttling Range.
PROGRAM
RELAY 1
SENSOR
Fig. 30. Program - Sensor.
PROGRAM
RELAY 1
HEAT/COOL
Fig. 31. Program - Heat/Cool.
MENU
PROGRAM
RELAY 1
DIFFRNTL
20
o
F
ENTER
DIFFERENTIAL
FOR
RELAY 1
M24495
MENU
PROGRAM
RELAY 1
SENSOR
SENSOR A
SENSOR B
SELECT
SENSOR FOR
RELAY 1
M24496
MENU
PROGRAM
RELAY 1
HEAT/COOL
HEAT
COOL
SELECT
HEAT/COOL
FOR
RELAY 1
M24497
T775A/B/M SERIES 2000 CONTROLLER
1.2.2. DIFFERENTIAL or THROTTLING RANGE
Differential is used for Relay outputs and Throttling Range
is used for Modulating outputs.
1. From the menu, use the
light THROT RNG or DIFFERNTL.
2. Press the
button to display the throttling range
value.
3. Use the
and
desired value.
Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C).
4. Press the
button to accept the value and display
the next option.
In heating mode, the Differential is below the setpoint.
The relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint.
The relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.
The Throttling Range brackets the setpoint setting, e.g., if
the setpoint is 72°F and the throttling range is 10°F, then
the effective throttling temperature range is 67°F to 77°F.
This applies to both modulating outputs and floating
outputs.
1.2.3. SENSOR
1. From the menu, use the
light SENSOR.
2. Press the
button to display the sensor selections.
3. Use the
and
4. Press the
button to accept the highlighted sensor
and display the next option.
1.2.4. HEAT/COOL
1. From the menu, use the
light HEAT/COOL.
Default: HEAT
2. Press the
button to display the heat and cool
selections.
3. Use the
and
4. Press the
button to accept the highlighted selec-
tion and display the next option.
15
and
buttons to high-
buttons to increase/decrease the
and
buttons to high-
buttons to select Sensor A or B.
and
buttons to high-
buttons to select Heat or Cool.
62-0254–03