Figure 15 - Installation Without Eu Meter - Honeywell STT700 STT700 User Manual

Temperature transmitter
Table of Contents

Advertisement

3.4.6.1.
If an EU meter is used, remove the shunt on the Lightning Protector. In all other cases, the
shunt must be present.
Remove the cover/cap of the housing (if applicable). The device fits on the top of the
transmitter module terminal block and the transmitter output screws (+ and -) fix
mechanically the device.
Attach the grounding wire to the ground screw in the housing. Connect a wire from the
transmitter enclosure to local Earth Ground. Use size 14 AWG or 2.0mm2 bare or green
covered wire.
If an EU meter is used, wire according to Figure
Connect the 4 – 20mA loop to the + and – terminal screws of the surge protection and close
the cap of the housing.
Page 22
Installation
Figure 15 – Installation without EU Meter
STT700 Temperature Transmitter User's Manual
16.
Revision 1