Honeywell Ex-Or MLS2000DF Installation And Commissioning Instructions page 3

Digital detector

Advertisement

Commissioning Detectors Using the QuickSet Pro
It is important that the Programmer be held perpendicular and at a distance of between 0.5m and 2m from the detector.
1. Switch on by pressing any button (and unlock with top left rectangular button).
2. Point programmer at the detector and press the DOWNLOAD button. The programmer will confirm the product's
identity and call up the correct menu of parameters and their current settings.
3. Use a combination of UP, DOWN, FORWARD and BACK buttons to navigate the parameter menu, selecting options
for each shown.
4. When options for all parameters have been selected, point the programmer at the detector and press the UPLOAD
button. The luminaire(s) will switch off briefly during the programming process and the programmer shows DATA
OK to confirm operation.
5. After a short period of inactivity (default 5 minutes), the programmer hibernates retaining the most recent settings.
Parameter
Options
Power Up
On / Off
Response
Auto, Manual/Bus, Manual only
Off Delay
1 min - 96 hrs, 10-sec (walk-test), Disabled 20 mins
On Sensitivity
0-100
Bus Connect
Yes / No
1st - 4th Zone
Address 1-100; -- (no zone); Common 1-3
Corridor 1 & 2
0-100; -- (no zone); Building
Global 1 & 2 Rx
Yes / No
Manual Input
Shared / Local
Start Lamps
Max / Min
Entry Scene
1-6
Bright Out
Yes / No
Dimming
Reg 50%-Reg100%
Lamp Max
10%-100%
Fade to Off
Yes / No
When Vacant
Off / Min / Reg <25% / Scene 6
Set-point Low
0-1023
Set-point High
0-1023
Additional feature accessible under Utilities on QuickSet Pro:
100 Hour Burn-In Burn-in 100 hrs / Cancel / Resume
Pre-Set
Notes
Sets the luminaire state at power up irrespective of occupancy.
On
Useful in reducing start-up load following power cut. Power-
up off - responds to occupancy after 30 seconds.
Auto
If set to Auto, the presence detector switches the luminaire on
and off automatically. If set to Manual Only, it can only be
turned on by using OneSwitch or the hand-held controller. If
set to Manual/Bus, an MLS Bus turn-on command for a Zone
to which th
The time for which the luminaire will stay on following the last
detected movement. Also 10-second setting for walk-testing.
100
Sensitivity to movement when area is occupied. 100 = max
Yes
Do/Do not Signal/Receive on MLS Bus.
No Zone
Individual Zones influencing and being influenced by this
detector.
No Zone
Zone ranges influencing and being influenced by this detector.
No
Respond to selective load shedding.
Local
Do/Do not signal OneSwitch commands across the MLS Bus.
Max
Sets the level at which the lamps strike when turning on.
Sets which scene is recalled when unoccupied area is
Scene 1
entered.
No
If set to yes, movement fails to refresh the off delay if ambient
light level exceeds 125% of set level and the luminaire will
switch off when the off delay has elapsed. NB: Dimming must
be set to 100%.
100%
Can be set to operate between 50% and 100% ballast output
from max down to a bottom-end limit when working on
photocell control.
Can be set to limit the absolute maximum output of the ballast
100%
in all operating modes.
No
When no presence is detected, and after the off delay period,
the lamps can fade out instead of switching off (approx 80
seconds to fade from 100% to 0%).
Off
Options for a vacant area after it has timed out. Luminaires
can turn off, remain at minimum output, or regulate with a 25%
output limit, until the next period of occupancy. If programmed
to remain at minimum, to regulate below 25% or go to scene
6, the
1023
Aiming point as photocell adjusts ballast output.
1023
Level above which photocell switches its output off (only if
Bright Out = Yes).
0 hr
See Application Note: AN4028