Honeywell Fire-Lite Alarms MS-9200UDLS Manual page 4

Intelligent addressable facp with built-in communicator
Hide thumbs Also See for Fire-Lite Alarms MS-9200UDLS:

Advertisement

MMF-300: Addressable Monitor Module for one zone of nor-
mally-open dry-contact initiating devices. Mounts in standard
4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-
line resistor. Module may be configured for either a Style B
(Class B) or Style D (Class A) IDC.
MDF-300: Dual Monitor Module. Same as MMF-300 except it
provides two Style B (Class B) only IDCs.
MMF-301: Miniature version of MMF-300. Excludes LED and
Style D option. Connects with wire pigtails. May mount in
device backbox.
MMF-302: Similar to MMF-300, but may monitor up to 20 con-
ventional two-wire detectors. Requires resettable 24 VDC
power. Consult factory for compatible smoke detectors.
CMF-300: Addressable Control Module for one Style Y/Z
(Class B/A) zone of supervised polarized Notification Appli-
ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.
Notification Appliance Circuit option requires external 24 VDC
to power notification appliances.
CRF-300: Addressable relay module containing two isolated
sets of Form-C contacts, which operate as a DPDT switch.
Mounts directly to a 4.0" (10.16 cm.) box, surface mount using
the SMB500.
BG-12LX: Addressable manual pull station with interface mod-
ule mounted inside.
I300: Fault Isolator Module. This module isolates the SLC loop
from short circuit conditions (required for Style 6 or 7 opera-
tion).
SMB500: Used to mount all modules except the MMF-301 and
M301.
MMF-300-10: Ten-input monitor module. Mount one or two
modules in a BB-2F cabinet (optional). Mount up to six mod-
ules on a CHS-6 chassis in a BB-6F.
Page 4 of 6 — DF-60415:C • 12/17/2009
MMF-302-6: Six-zone interface module for compatible conven-
tional two-wire detectors. Mount one or two modules in a BB-
2F cabinet (optional). Mount up to six modules on a CHS-6
chassis in a BB-6F.
CMF-300-6: Six-circuit supervised control module. Mount one
or two modules in a BB-2F cabinet (optional). Mount up to six
modules on a CHS-6 chassis in a BB-6F.
CRF-300-6: Six Form-C relay control module. Mount one or
two modules in a BB-2F cabinet (optional). Mount up to six
modules on a CHS-6 chassis in a BB-6F.
NOTE: 1) For more information on Compatible Addressable
Devices for use with the MS-9200UDLS Rev 2, see the following
data sheets (document numbers): AD355 (DF-52386), BG-12LX
(DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-52374),
CMF/CRF Series (DF-52130), CP355 (DF-52383), D350PL/
D350RPL (DF-52398), H355 Series (DF-52385), I300 (DF-52389),
MMF-300 Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347),
MMF-302-6 (DF-52356), SD355/SD355T (DF-52384). 2) Legacy
300 Series detection devices such as the CP300/CP350,
SD300(T)/SD350(T) and older modules such as the M300, M301,
M302, C304, and BG-10LX are not compatible with LiteSpeed
polling. If the SLC contains one of these devices, polling must be
set for standard LiteSpeed protocol. Please consult factory for fur-
ther information on previous 300 Series devices.
Wiring Requirements
While shielded wire is not required, it is recommended that all
SLC wiring be twisted-pair to minimize the effects of electrical
interference. Wire size should be no smaller than 18 AWG
(0.78 mm²) and no larger than 12 AWG (3.1 mm²). The wire
size depends on the length of the SLC circuit. Refer to the
panel manual for wiring details.

Advertisement

loading

This manual is also suitable for:

Fire-lite alarms ms-9200udlse