Honeywell Fire-Lite Alarms MS-9200UDLS Manual page 2

Intelligent addressable facp with built-in communicator
Hide thumbs Also See for Fire-Lite Alarms MS-9200UDLS:

Advertisement

• Real-time clock/calendar with automatic daylight savings
control.
• Detector sensitivity test capability (NFPA 72 compliant).
• History file with 1,000-event capacity.
• Maintenance alert warns when smoke detector dust accu-
mulation is excessive.
• Automatic device type-code verification.
• One person audible or silent walk test with walk-test log and
printout.
• Point trouble identification.
• Waterflow (nonsilenceable) selection per monitor point.
• System alarm verification selection per detector point.
• PAS (Positive Alarm Sequence) and presignal delay per
point (NFPA 72 compliant).
NOTE: Only detectors may participate in PAS.
SLC LOOP:
• SLC can be configured for NFPA Style 4, 6, or 7 operation.
• SLC supports up to 198 addressable devices per loop (99
detectors and 99 monitor, control, or relay modules).
• SLC loop maximum length 10,000 ft. (3,000 m.).
See installation manual for wire tables.
NOTIFICATION APPLIANCE CIRCUITS (NACS):
• Four onboard NACs with additional NAC capability using
output control modules (CMF-300 or CMF-300-6). The four
Class B NACs can be converted to two Class A NACs with
NACKEY (included).
• Silence Inhibit and Auto Silence timer options.
• Continuous, March Time, Temporal or California code for
main circuit board NACs with two-stage capability.
• Selectable strobe synchronization per NAC.
• 2.5 amps maximum per each NAC circuit.
NOTE: Maximum 24VDC system power output is shared among
all NAC circuits and 24VDC special-application auxiliary power
outputs. Total available output is 3.0 amps. Using the optional
XRM-24B transformer increases 24VDC output to 6.0 amps.
PROGRAMMING AND SOFTWARE:
• Autoprogram (learn mode) reduces installation time.
• Custom English labels (per point) may be manually entered
or selected from an internal library file.
• Three Form-C relay outputs (two programmable).
• 99 software zones.
• Continuous fire protection during online programming at the
front panel.
• Program Check automatically catches common errors not
linked to any zone or input point.
• OFFLINE PROGRAMMING: Create the entire program in
your office using a Windows®-based software package
(order programming kit PS-Tools, separately). Upload/
download system programming locally to the MS-
9200UDLS(E) Rev 2 in less than one minute.
• USB programming with standard Male-A to Male-B cable.
User interface
LED INDICATORS
• AC Power (green)
• Fire Alarm (red)
• Supervisory (yellow)
• Alarm Silenced (yellow)
• System Trouble (yellow)
Page 2 of 6 — DF-60415:C • 12/17/2009
• Maintenance/Presignal (yellow)
• Disabled (yellow)
• Battery Fault (yellow)
• Ground Fault (yellow)
KEYPAD CONTROLS
• Acknowledge/Step
• Alarm Silence
• Drill
• System Reset (lamp test)
• 16-key alpha-numeric pad (similar to telephone keypad)
• 4 cursor keys
• Enter
Product Line Information
MS-9200UDLS Rev 2: 198-point addressable Fire Alarm Con-
trol Panel, one SLC loop. Includes 80-character LCD display,
single printed circuit board mounted on chassis, and cabinet.
120 VAC operation.
MS-9200UDLSE Rev 2: Same as MS-9200UDLS Rev 2,
except with 240 VAC operation.
4XTMF Reverse Polarity Transmitter Module: Provides
supervised output for local energy municipal box transmitter,
alarm, and trouble.
PK-CD: Contains PS-Tools Programming software for Win-
dows®-based PC computer (cable not included).
DP-9692: Optional dress panel for MS-9200UDLS Rev 2.
TR-CE: Trim Ring for semi-flush mounting.
BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
BB-55F: Battery box, houses two 55 AH batteries.
CHG-75: Battery charger for lead-acid batteries with a rating
of 25 to 75 AH.
CHG-120F: Remote battery charging system for lead-acid bat-
teries with a rating of 55 to 120 AH. Requires additional BB-
55F for mounting.
BAT Series: Batteries, see data sheet DF-52397.
XRM-24B(E): Optional transformer. Increases system power
output to 6.0 amps. Use XRM-24BE with MS-9200UDLS Rev
2(E).
PRT/PK-CABLE: Cable printer/personal computer interface
cable; required for printer or for local upload/download pro-
gramming.
PRN-6F: UL listed compatible event printer. Uses tractor-fed
paper.
IPDACT-2/2UD,
IPDACT
Mounts in bottom of enclosure with optional mounting kit (PN
IPBRKT). Connects to primary and secondary DACT tele-
phone output ports for internet communications over customer
provided ethernet internet connection. Requires compatible
Teldat VisorALARM Central Station Receiver. Can use DHCP
or static IP. (See data sheet df-60407 or df-52424 for more
information.)
IPBRKT: Mounting kit for IPDACT-2/2UD in common enclo-
sure.
IPSPLT: Y-adaptor option allows connection of both panel
dialer outputs to one IPDACT-2/2UD cable input.
COMPATIBLE ANNUNCIATORS
ANN-80(-W): LCD Annunciator is a remote LCD annunciator
that mimics the information displayed on the FACP LCD dis-
Internet
Monitoring
Module: