Recessed Mounting Instructions - Honeywell ECS Series Installation And Operation Manual

Emergency communication system
Table of Contents

Advertisement

ECS Series Emergency Communication System Installation Manual
3.4.7

Recessed Mounting Instructions

This section describes how to recess mount the cabinet IFP-100ECS, IFP-1000ECS or IFP-2000ECS
into a wall. To recess mount the cabinet you will need to have the optional trim ring P/N VIP-TR
(ordered separately). Follow these steps to recess mount the cabinet:
1. Remove the cabinet door and the dead front panel. See Section 3.4.7.1.
2. Cut a recess hole. There should be 1.5" to 1.75" of cabinet extruding from the wall, this should be
measured from either the top edge or bottom edge to the exterior side of the sheet rock. (See Fig-
ure 3-9.)
Do not insert the cabinet deeper than recommend above. If the cabinet is mounted to deep you will not be able to re-attach
the door assembly.
3. Mount the cabinet to wall studs by inserting a screw through the cabinets side mounting holes into
the wall stud.
Trim Ring
Trim Ring
Mounting
Hole
Side View of Cabinet
and Trim Ring
Important!
Cabinet
Mounting Hole
Trim Ring
Mounting
Hole
Figure 3-9 Detail of Flush Mounting with Trim Ring
Sheet Rock
1.5 to 1.75"
3-10
151455
Mounting
Studs
Cabinet
Mounting Hole
Sheet Rock