Honeywell VS821 Quick Start Manual
Honeywell VS821 Quick Start Manual

Honeywell VS821 Quick Start Manual

Millivoltage combination gas controls

Advertisement

Quick Links

APPLICATION
The VS820 and VS821 are used on gas fired, standing
pilot appliances with 750 mV self-powered control systems.
The gas controls include a manual gas valve, safety shutoff,
single millivoltage automatic operator and pressure regula-
tor. Refer to Table 1 for capacity ratings and Table 2 for
pressure regulators and temperature ratings. Separate
TABLE 1—VS820 AND VS821 PIPE SIZE AND CAPACITY RATINGS.
MODEL
PIPE SIZE
VS821
1/2 x 3/8
VS820
1/2 x 1/2
1/2 x 3/4
3/4 x 3/4
VS820
1 x 1
High Capacity
Capacity is based on 1000Btuh/ft
a
at 0.25 kPa pressure drop]. Use conversion factors in Table 3 to convert for other gases.
Reducer fittings must be obtained locally.
b
TABLE 2—PRESSURE REGULATOR AND TEMPERATURE RATINGS.
MODEL
PRESSURE
TYPE
VS820A,H
Standard
VS821A
VS820C, VS821C
Step
VS820D
Hi-Low
VS820P
Step
VS820V
Standard
TABLE 3—GAS CAPACITY CONVERSION FACTORS.
SPECIFIC
TYPE OF GAS GRAVITY
Manufactured
0.60
Mixed
0.70
Propane
1.53
INSTALLATION
WHEN INSTALLING THIS PRODUCT...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in these instructions and on
the product to make sure the product is suitable for your
application.
3. Make sure installer is a trained, experienced service
technician.
4. After completing installation, use these instructions to
check product operation.
D.T.
Rev. 4-89
INLET x OUTLET
CAPACITY
cfh
m
3
110
3.1
225
6.4
250
7.1
335
9.5
600
17.0
, 0.64 sp gr natural gas at 1 in. wc pressure drop [37.3 MH/m
3
REGULATOR
MODEL
V5306A
V5307A
V5308A
V5307B
V5306A
MULTIPLY
LISTED CAPACITY BY
0.516
0.765
1.62
VS820A,C,D,H,P,V AND VS821A,C
MILLIVOLTAGE COMBINATION
GAS CONTROLS
models are available for natural and LP gas; the controls
cannot be field converted.
Power for the gas control and the control system is
provided by a 750 mV Powerpile generator. We recom-
mend the Q313 Thermopile Generator or the CS82, CS893,
CS894, or CS897 Pilot Burner Generators.
REDUCER FITTINGS
a
/hr
SIZE
3/4 x 1/2
1/2 x 3/8
3/4 x 1/2
3/4 x 1/2
1 x 3/4
1 x 3/4
TEMPERATURE RATING
°F
32 to 175
-40 to 175
WARNING
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE IN-
JURY, OR DEATH
Follow these warnings exactly:
1. Disconnect power supply before wiring to pre-
vent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at appliance service valve
before starting installation and perform Gas
Leak Test following installation.
3. Do not bend pilot tubing at control or at pilot
after compression fitting has been tightened.
Gas leakage at the connection fitting may
result.
4. Always install sediment trap in gas supply line
to prevent contamination of gas control.
5. Do not force gas control knob. Use only your
hand to turn gas control knob. If the knob will
not operate by hand, the control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.
b
CAPACITY
cfh
m
3
/hr
225
6.4
110
3.1
250
7.1
225
6.4
503
14.2
450
12.7
, 0.64 sp gr natural gas
3
°C
0 to 79
-40 to 79
Form Number 95-6994—8
©Honeywell Inc. 1989

Advertisement

loading

Summary of Contents for Honeywell VS821

  • Page 1 VS820A,C,D,H,P,V AND VS821A,C MILLIVOLTAGE COMBINATION GAS CONTROLS APPLICATION The VS820 and VS821 are used on gas fired, standing models are available for natural and LP gas; the controls pilot appliances with 750 mV self-powered control systems. cannot be field converted.
  • Page 2: Choose Location

    CAUTION DROP PIPED Never apply a jumper across (or short) valve coil HORIZONTAL CONTROL terminals. This may burn out thermostat heat anticipa- SUPPLY tor. RISER IMPORTANT These gas controls are shipped with protective seals CONTROL PIPED over inlet and outlet tappings. Do not remove seals 3 IN.
  • Page 3 Follow appliance manufacturer’s wiring instructions, if 3. Thread pipe the amount shown in Table 4 for insertion available, or use general instructions provided below. Where into control. DO NOT THREAD PIPE TOO FAR. Valve instructions differ, follow appliance manufacturer instruc- distortion or malfunction may result if the pipe is inserted too tions.
  • Page 4: Startup And Checkout

    STARTUP AND CHECKOUT To adjust: 1. Remove pilot adjustment cover screw. Refer to Fig. 2 WARNING or 3. 2. Turn inner adjustment screw clockwise to de- crease or counterclockwise to increase pilot flame. FIRE OR EXPLOSION HAZARD 3. Always replace cover screw after adjustment and tighten firmly to ensure proper operation.
  • Page 5 achieved by adjusting the gas control, check gas control inlet pressure using a manometer at inlet pressure tap. If inlet pressure is in the nominal range (refer to Table 5), KNOB MARKINGS replace gas control. Otherwise, take the necessary steps (TOP VIEW) to provide proper gas pressure to the control.
  • Page 6 CHECK SAFETY SHUTDOWN PERFORMANCE IF MAIN BURNER WILL NOT COME ON WITH CALL FOR HEAT WARNING 1. Make sure gas control knob is in the ON position. 2. Adjust thermostat several degrees above room tem- perature. FIRE OR EXPLOSION HAZARD 3.
  • Page 7 3. Remove control access panel. lit. If it goes out, repeat steps 5-10. 4. Push in gas control knob (refer to Fig. 3 or 4) slightly 10.Replace pilot access panel. and turn clockwise to OFF. 11.Turn gas control knob counterclockwise NOTE: Knob cannot be turned from PILOT to OFF unless 12.Replace control access panel.