ABB Relion 670 Series Applications Manual page 509

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
Setting parameter
MaxI2tW1
MaxI2tW2
MaxI2tW3
MaxI2tCmlW1
MaxI2tCmlW2
MaxI2tCmlW3
17.12.4.3
Application example for OHL
Additionally, the PTRSTHR (51TF) function can be used to monitor faults on OHL. In such cases, the
OHL current and voltage shall be connected to W1 inputs. In case of one-and-a-half breaker
configuration, W1 and W2 currents shall be used.
For such applications, the PTRSTHR (51TF) function can be triggered either by the set phase
current level or externally by the START or TRIP signal from the distance protection. As a result, a
summary list that provides an overview about all through faults seen by the IED will be available on
the local HMI.
17.13
Current harmonic monitoring CHMMHAI(ITHD)
17.13.1
Identification
Function description
Current harmonic monitoring
17.13.2
Application
In order to maintain the power quality for better supply, harmonics in the system must be
monitored. Due to the nonlinear loads connected to the system, harmonics (apart from
fundamental frequency component) are generated and thereby the system voltage is distorted.
Voltage distortion appears to have a little effect on operation of nonlinear loads connected, either
phase-to-phase or phase-to-neutral. Current distortion is limited at the point of common coupling
PCC to control the harmonic current from the utility to the consumer. Thereby, the voltage
distortion must be limited in order to prevent it from spreading to other facilities.
Bay control REC670
Application manual
IEC 61850
identification
CHMMHAI
© Copyright 2017 ABB. All rights reserved
Select value
2
696 8
 
 
2
2 62.0
kA s
1000000
IECEQUATION18025 V1 EN-US
2
1255 8
 
 
2 201.608
1000000
IECEQUATION18051 V1 EN-US
2
577 8
 
 
2 45.615
kA s
1000000
IECEQUATION18052 V1 EN-US
 
2
62.0 10 620 kA s
IECEQUATION18053 V1 EN-US
 
201.608 10 2016.08 kA s
IECEQUATION18054 V1 EN-US
 
2
42.615 10 426.15 kA s
IECEQUATION18055 V1 EN-US
IEC 60617
ANSI/IEEE C37.2
identification
device number
ITHD
ITHD
Section 17
Monitoring
2
kA s
2
2
GUID-FDD5C618-93B0-4DE7-A7E4-D997E2087769 v1
GUID-692151F8-812B-4B32-AE86-E7A4E4B0101B v1
GUID-C7863D78-34DB-42E5-90FE-6483EDAAF319 v1
GUID-987BCB6C-C559-42EE-9AAB-5F71189A58C6 v2
503