1MRK 511 401-UUS F
MODEINT (integer)
A start of a new auto reclosing cycle during the set "reset time" is blocked when the set number of
reclosing shots have been reached.
14.2.2.14
External selection of auto reclosing mode
The auto reclosing mode can be selected by use of available logic function blocks. Below is an
example where the choice of mode,
function key at the front of the IED, but alternatively there can for example, be a physical selector
switch on the front of the panel which is connected to a binary to integer function block
(BTIGAPC).
The connection example for selection of the auto reclosing mode is shown in Figure 119.
INTONE
3
1/3
ANSI09000168 V1 EN-US
Figure 119: Selection of the auto-reclose mode from a hardware functional key in front of the
14.2.2.15
Auto reclosing reset timer
tReset timer defines the time it takes from issue of the breaker closing command, until the
The
auto recloser resets. Should a new trip occur during this time, it is treated as a continuation of the
first fault. The reclaim timer is started when the circuit breaker closing command is given.
Bay control REC670
Application manual
ARMode
3
1/2ph
4
1ph + 1*2ph
5
1/2ph + 1*3ph
6
1ph + 1*2/3ph
SLGGIO
PSTO
NAME1
NAME2
IED
© Copyright 2017 ABB. All rights reserved
Type of fault
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
ARMode = 3ph or ARMode = 1/2/3ph , is done from a hardware
SMBRREC (79)
SWPOSN
MODEINT
1st shot
2nd-5th shot
1ph
3ph
2ph
3ph
.....
.....
1ph
3ph
2ph
.....
.....
.....
1ph
3ph
2ph
3ph
3ph
.....
1ph
3ph
2ph
.....
3ph
.....
ANSI09000168_1_en.vsd
Section 14
Control
M12391-241 v5
M12391-202 v4
297