1MRK 511 401-UUS F
3PT1, 3PT2, 3PT3, 3PT4 and 3PT5
Indicates that three-pole auto reclosing shots one to five are in progress. The signals can be used
as an indication of progress or for own logic.
ABORTED
ABORTED output indicates that the auto recloser is inhibited while it is in one of the following
The
internal states:
inProgress: auto recloser is started and dead time is in progress
reclaimTimeStarted: the circuit breaker closing command has started the reclaim timer
wait: an auto recloser, acting as slave, is waiting for a release from the master to proceed with
its own reclosing sequence
ACTIVE
Indicates that the auto recloser is active, from start until end of reset time.
BLOCKED
Indicates that auto recloser is temporarily or permanently blocked.
CLOSECMD
Connect to a binary output for circuit breaker closing command.
COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3, COUNT3P4 and
COUNT3P5
Indicates the number of auto reclosing shots made for respective shot.
COUNTAR
Indicates the total number of auto reclosing shots made.
INHIBOUT
INHIBIT input is activated it is reported on the INHIBOUT output.
If the
INPROGR
Indicates that an auto recloser sequence is in progress, from start until circuit breaker close
command.
MODE
When a valid integer is connected to the
invalid and the
integer on the
corresponding
PERMIT1P
Permit single-pole trip is the inverse of
connection to external protection or trip relays. In case of a total loss of auxiliary power, the
output relay drops and does not allow single-pole trip.
Bay control REC670
Application manual
MODEINT input value will be used instead. The selected mode is reported as an
MODE output. The six possible modes are described in Table
MODEINT integer value.
© Copyright 2017 ABB. All rights reserved
MODEINT input, the selected ARMode setting will be
PREP3P . It can be connected to a binary output relay for