Trouble shooting 31
OUTDOOR UNIT Error Method:
Pressure Switch Error
Detective Actuators:
High pressure switch
Main PCB
Forecast of Cause :
1. High pressure switch connector disconnection, open
2. High pressure switch characteristics failure
3. Main PCB failure
Check Point 1 : Check the high pressure switch connection state
Connector and wiring connection state check
Cable open check
OK
Check Point 2 : Check the high pressure switch characteristics
Switch characteristics check
* For the characteristics of high pressure switch, refer to below.
OK
Check Point 3 : Replace Main PCB
, and execute the check operation again.
Change Main PCB
Type of contact
C
H
Pressure
Characteristics of pressure switch
Contact : Short
Open
Contact : Open
Short
Indicate or Display:
Indoor Unit : Operation lamp: 8 time Flash,
Timer lamp: 6 time Flash
Economy lamp : Continuous flash.
ERROR CODE : [E : 86]
Detective details:
When the power was turned on, "high pressure switch : open" was failure.
(CN120)
Pressure switch
4.2
0.15MPa
3.2
0.15MPa