Sensor, sounder, speech & visual alarm

Advertisement

Description & Commissioning
Device
Heat sensor variant -
(With Speech & VAD)
S4-720-V-VAD-HPR
S4-720-V-VAD-HPW
Optical sensor -
³
# - factory default settings
S-Quad Dual Optical Heat & Optical Heat sensor STATES
STATE
Definition / Class
STATE 3
High sensitivity optical,
Class A1 heat
Normal sensitivity with no optical
STATE 4
spike protection, Class A1 heat
STATE 0# Normal sensitivity optical,
Class A1 heat
STATE 8
Delayed normal sensitivity optical,
Class A1 heat
STATE 7
Normal sensitivity optical,
Class A2S heat
STATE 5
Normal sensitivity optical,
Class B heat
Low sensitivity optical smoke ³,
STATE 2
Class A1 heat
Low sensitivity optical smoke ³,
STATE 11
Class B heat
Low sensitivity optical smoke ³,
STATE 6
Class BS heat
STATE 12 Class A1 heat only
STATE 15 No detection
# - factory default STATE. NOTE: All the Sensor STATES in the above table are LPCB approved to EN54-5 & EN54-7 with the
exception of STATES 2, 6 and 11 which are only approved to
may still be useful in certain applications.
S-Quad Dual Optical, Heat & CO sensor STATES
STATE
Definition / Class
STATE 1
High sensitivity optical, Class A1
heat, high sensitivity gas
10
LPCB
approved
STATES
S4-720
STATE 0 # Class A1 heat *
STATE 5
STATE 6
STATE 7
STATE 13
(With Sounder)
S4-780-S
STATE 0 # Normal sensitivity optical smoke
S4-715
STATE 2
STATE 3
STATE 4
STATE 8
Low sensitivity optical smoke sensing is not approved but may still be useful in certain applications.
Application in / Suitable for:
Clean area or environment, where early detection is
required.
General area as STATE 0 with less immunity to steam
and dust for ease of testing using artificial smoke in
normal operating mode, when test / commissioning
mode is not active.
General area.
General application in area with transient steam, dust
or smoke present
General application in area with low dust, smoke or
steam present, for fixed temperature operation that is
totally unaffected by transient temperature variation
Area having high ambient temperature with low dust,
smoke or steam present
Areas with moderate dust, smoke or heat during
working hours when used with timing function
Area having high ambient temperature, plus where
moderate dust, smoke or steam present
Area having high ambient temperature that changes,
plus moderate dust, smoke or steam present
Area where smoke, dust or steam occurs at times
The STATE 15 is no detection and is not part of LPCB approval.
Application in / Suitable for:
Clean area or environment where early detection is
required with false alarm reduction.
Meets ~ EN54-7 : 2000, A1:2002, A2:2006
* EN54-5 : 2000, A1:2002
Class B heat *
Class BS heat *
Class A2S heat *
Class A2 heat *
Low sensitivity optical smoke ³
High sensitivity optical smoke
Normal sensitivity (no spike) optical smoke
Medium sensitivity delayed optical smoke
.
.
³
EN54-5.
Low sensitivity optical smoke sensing is not approved but
S-Quad
Sensitivity
a-high- to-k-none
a
b
c
d
e
f
g
.
h
.
i
.
j
.
k
Sensitivity
a-high- to-i-none
4188-1073 issue 3_2-17_P2_S-Quad