Download Print this page

Installation - Honeywell NOTIFIER DSE3-23 Series Quick Start Manual

Optical and acoustic fire alarm device for indoor installation

Advertisement

 
1. Insert the head of a screwdriver in the slot as shown in Picture 2 and then press gently to lift the cover up a bit; 
2. Take off the cover from the tracks; 
3. Hang the sounder on the wall through the 4 fixing holes located on the sounder base (see Pict. 1) and using 4 pcs. of 5‐
mm wall plugs; 
4. In case of system with external pipes, use an adapter to connect all cables; 
5. Close the siren and fix the cover with the screw provided. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Pict. 1 
 
 
 
NOTES ABOUT THE DEVICE: 
 
A cable of 0,33 mm
of
cross sectional
The device must be installed by qualified staff only using proper tools and following the manufacturer's instruction provided 
in this installation sheet. Any other use rather than the one explained in this installation sheet can cause damaged! 
ATTENTION! The device must be powered using a control panel output featuring SELV tension and limited power. 
 
DSE3‐23 HW 
The device is classified as O. It is designed to cover a maximum volume with side A = 4 m, side B = 7 m, side C = 18 m (See 
Pict. 4). 
It can be installed on a wall at 4 m of altitude or on a ceiling at h = 7 m maximum. 
For wall installation, the device must be installed with the long side perpendicular to the floor and the strobe flashing unit 
looking downwards. Maximum installation height is 4 m, the illumination coverage will be 9 m on the right and 9 m on the 
left and 7 m on front. 
For ceiling installation, the device must be installed with the long side perpendicular to the wall and the strobe flashing unit 
looking  towards  the  space  to  be  illuminated.  Consider  that  the  wall  on  the  side  without  flash  will  be  not  illuminated. 
Maximum installation height is 7 m; the illumination coverage will be 4 m at the front and 9 m at the right and 9 m on the 
left. 
              

Installation:

Fixing 
Fix the cover with the 
Holes 
screw 
Insert the screwdriver 
here to open the 
sounder 
 
(AVG 22) minimum, must be used. 
 
 
Pict. 4bis: mount the long side of the 
 
device perpendicular with respect the 
 
wall of the corridor 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Pict. 2 