SECTION 6. FOUR-WIRE GROUND
FAULT OPTION
The ground fault option for four-wire installations
requires the installation of an additional current
sensor on the neutral bus in the equipment. The
sensor is connected to the trip unit through the
connector provided in the wiring harness.
1. Mount the neutral sensor on the outgoing neutral
lead, normally in the bus or cable compartment
in the equipment. Figures 20 and 21 show the
sensor outlines for the 800 A and 1600 A frame
sizes, respectively.
2. Connect the neutral sensor wire harness to the
correct taps on the sensor. To maintain the same
polarity as the phase sensors, connect the white
wire to the common terminal, black to the tap.
3. Route the wires through the equipment and con-
nect to the two-pin connector on the trip unit wir-
ing harness, routed through the rear of the
breaker with the CT wires. The wires should be
tied to the breaker frame in an easily accessible
location.
Figure 20. Neutral sensor outline for LA-800 breakers..
15