Honeywell FIRE-LITE ALARMS TS540/1 Quick Start Programming Manual page 2

Ipdact ip communicator

Advertisement

3. Physical Connections
FROM AP
PHONE
MALE PLUG
CONNECTOR
IPDACT
TO AP
INPUT
GND / +24V
Ethernet Network
(RJ45)
4. IPDACT Default Configuration
Through a short circuit in the IPDACT P2 jumper during the start up process, you can
configure the IPDACT with the default factory settings. The process for this is as follows:
1)
switch off the IPDACT
2)
short circuit the jumper with the supplied berg header,
3)
switch on the device,
4)
maintain the jumper short circuited during the first A-D LEDs burst (the LEDs
turn on and off) and undo the short circuit during the second burst.
If the process has executed successfully, the IPDACT will display a third burst indicating the
default configuration has been activated.
PSTN
TO AP
OUT NC
NOTE: Connections to
the TO AP terminal
are interchangeable
RJ-31, PRIMARY FIRE
PANEL PHONE LINE
Connects to...
To the PRIMARY FIRE PANEL PHONE LINE.
The connections to the TO AP terminal are interchangeable.
Connect the supplied 1K resistor
To the 24 VDC power supply from the Fire Alarm Panel (or other
electric supply) This should be 24 VDC from Fire Alarm Panel
To a broadband modem/router or a network switch/hub for internet
access.
OUT NO
INPUT
TAMPER
1K EOLR
Connect to the
+24VDC
Nonresetable
Power Supply
RJ45
ETHERNET
GND+12/24V
Female JACK
Connect to
custormer's supplied
network equipment
(Cat 5 cable)
NON RST
POWER