Honeywell FIRE-LITE ALARMS TS540/1 Quick Start Programming Manual

Honeywell FIRE-LITE ALARMS TS540/1 Quick Start Programming Manual

Ipdact ip communicator

Advertisement

Quick Links

Quick Start Programming Guide using a PC Serial Port
1
. Requirements
Alarm Panel
"Contact Id" compatible panel with tone dialing.
Existing PSTN Service (for backup communication lines).
PC with RS-232 serial port.
Console cable for the IPDACT.
Consumption
IPDACT ver 2 (TS-540/X) (24V)
Internet Access
Either a static IP address (always the same) or a dynamic IP address (could be different every time
a connection is made) are possible.
2. Checklist¹
a.
IPDACT console access password (default is 24680)
b.
Installer password, required to execute the register command.
c.
IP address, subnet mask and gateway for IPDACT
d.
IPDACT account number or client number.
e.
IP address, and UDP Port number of the VisorALARM central station
1
Please obtain the following information from your central monitoring station.
2
If you have a DHCP server in the network to which the IPDACT connects, these parameters can be obtained automatically.
IPDACT
IP Communicator
IPDACT Dm 371-I
Model TS540/1
Idle
100mA
Alarm
120mA
2
Transient
300mA

Advertisement

loading

Summary of Contents for Honeywell FIRE-LITE ALARMS TS540/1

  • Page 1 IPDACT IP Communicator IPDACT Dm 371-I Quick Start Programming Guide using a PC Serial Port Model TS540/1 . Requirements Alarm Panel • “Contact Id” compatible panel with tone dialing. • Existing PSTN Service (for backup communication lines). • PC with RS-232 serial port. •...
  • Page 2 3. Physical Connections RJ45 ETHERNET FROM AP PHONE PSTN TO AP OUT NC OUT NO INPUT TAMPER GND+12/24V Female JACK NOTE: Connections to the TO AP terminal are interchangeable 1K EOLR Connect to custormer’s supplied network equipment Connect to the (Cat 5 cable) +24VDC Nonresetable...
  • Page 3 5. Serial Port Programming In order to use the serial port, you need to connect the cable designed to this end which must be obtained either from Firelite or from an authorized distributor. The following figures show the cable and the connection mode to the IPDACT. Connect the serial cable to the IPDACT as shown above, the other end to a PC serial port and use a terminal emulation program (Windows HyperTerminal for example) configuring the serial port to 9600 bps, 8 data bits, 1 stop bit, without parity and no flow control.
  • Page 4 Press the “c” key followed by the ENTER. You will be asked for the gateway IP address. Insert the value indicated for the parameter and then press ENTER. OK should now appear on the PC display which will then show the list of parameters that appear in option c) the value that has just been entered.