Honeywell Notifier FAAST LT NFXI-ASD Series Quick Installation Manual page 7

Table of Contents

Advertisement

Table 4: Front Panel Indicators and Fault Descriptions
INDICATOR
ACTION
CHANNEL 1/2 ALARM
ON Red
(Set by panel)
1 BLINK Green
(Polled by panel)
CHANNEL 1/2 PRE-
ON Yellow
ALARM
SMOKE LEVEL 1/2
ON Yellow
(Set by panel)
CHANNEL 1/2 MODULE
ON
BLINK
FAULT
ON Yellow
POWER
ON Green
POWER FAULT
ON Yellow
CHANNEL FLOW
ON Green
INDICATORS 1/2
LOW FLOW
ON
INPUT
1 BLINK
SENSOR
2 BLINKS
ASPIRATOR
ON
1 BLINK
2 BLINKS
DISABLE
1 BLINK
SYSTEM
1 BLINK
2 BLINKS
3 BLINKS
TEMPERATURE
1 BLINK
2 BLINKS
SOUNDER
1 BLINK
FILTER
1 BLINK
HIGH FLOW
ON
In case of simultaneous alerts/faults on the same LED, priority order is: ON (Highest), 1 blink, 2 blinks, 3 blinks (Lowest)
Note: The channel alarm and smoke level LEDs are under the
control of the CIE (Fire Panel).
Front Panel Buttons
The front panel has 3 user buttons: TEST, RESET and DISABLE.
These buttons are used to enter the pass-code which then allows
the user to carry out simple test functions.
Note: In Remote Maintenance and Service Mode, these buttons
are always disabled.
INITIALIZATION
N200-102-00
WARNING OR TROUBLE
Channel is in alarm (relay is
set ON with no delay)
When sensor is polled
Channel is in pre-alarm
Led number indicates sensor
alarm level reached
Module communication
Common or multiple faults
FAAST LT is powered
Low power alert / high power
fault
The LED indicates the air flow
for a channel:
-
Centre = normal flow
-
Left = flow low;
(-20% at extreme)
-
Right = flow high;
(+20% at extreme)
Low flow fault
External input fault
Sensor communication fault
Air flow sensor fault
Flow initialization fault
10
Fan fault
Alarms & alerts not reported
9
Wrong configuration
EEPROM fault
8
Real time clock fault
Low temperature alert
High temperature alert
7
Sounder fault
Filter alert at set date
High flow fault
6
5
4
3
2
SMOKE
1
LEVEL 1
FAULT
Figure 12: User Interface Buttons
COMMENT / ACTION
Default setting
Not when in alarm
(only with panels using Advanced Protocol)
Only numbers 1 – 9 used (only with panels using
Advanced Protocol).
Displays Yellow when initialising
Check the power supply voltage.
On 2 channel unit:
Upper row = Ch1
Lower row = Ch2
Check filter; check pipe network for blockages.
Not used with default settings
ALARM
Check sensor addresses and installation;
replace sensor.
Try to restart device.
PREALARM
Check filter; check pipe network for blockages;
try to restart device.
10
Try to restart device.
Returns to Maintenance then Normal operation
after 60min (default)
9
Flashes all FAULT LEDs; try to restart device.
Check power supply voltage. Try to restart
device
8
RTC is corrupted or time reading failed.
Check the air flow temperature
Check the air flow temperature
7
Check the sounder circuit and the EOL
No date set as default
Check pipe network for breaks or leaks.
6
5
4
3
2
1
7
SMOKE
LEVEL 2
INITIALIZATION
POWER
FAULT
I56-3947-200