Download Print this page

ABB ACH580-01 V R Series Instructions Manual page 5

Base drive replacement

Advertisement

REPLACEMENT INSTRUCTIONS | ACH580-01 VXR UL TYPE 1 , R2/R3/R4
Step
Instruction
14
CAUTION! Use two people to install the drive.
Slide the drive mounting holes over the bottom two (2) screws and
slide drive in place.
Using a T30 bit, replace the two (2) M6 screws that were removed
earlier.
Torque all four (4) mounting screws to 27 in-lb (3 Nm).
15
Secure the ground wire to the drive.
R2 & R3 Frame: Using a PZ3 bit, torque to 14 in-lb (1.5 Nm).
R4 Frame: Using a PZ3 bit, torque to 27 in-lb (3 Nm).
16
Connect the input wires (from fuse block) to the Input Terminals of
the drive.
Yellow U1 to L1
Black V1 to L2
Red W1 to L3
R2 Frame: Using a PZ2 bit, torque to 14 in-lb (1.5 Nm).
F3 Frame: Using a PZ2 bit, torque to 31 in-lb (3.5 Nm).
R4 Frame: Using a T20 bit, torque to 35 in-lb (4 Nm).
Connect the motor wires (from 1M contactor) to Motor Terminals of
the drive.
Yellow U2 to T1/U
Black V2 to T2/V
Red W2 to T3/W
R2 Frame: Using a PZ2 bit, torque to 14 in-lb (1.5 Nm).
F3 Frame: Using a PZ2 bit, torque to 31 in-lb (3.5 Nm).
R4 Frame: Using a T20 bit, torque to 35 in-lb (4 Nm).
Diagram
5

Advertisement