A.2 Door Holder Device
The following UL listed door holder can be used with the RPS-1000: ESL DHS-1224
A.3 Two-Wire Smoke Detectors
Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table
is organized by manufacturer. The columns show the number of detectors per loop
that can be used.
The maximum number of smoke detectors per zone is determined by both the current draw and the
impedance of the smoke detector. If too many smoke detectors are used on any zone, false alarms
could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed in
that configuration.
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the
maximum reset time of the smoke detector.
Table A-2 lists two-wire smoke detectors that are compatible with the RPS-1000
panel. The table is organized by manufacturer. The columns show the number of
detectors per loop that can be used.
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer
55000-350 (45681-200)
Apollo
55000-250 (45681-200)
DS200 (MB200-2W)
DS200HD (MB200-2W)
DS230
DS250 (MB2W or MB2WL)
Detection Systems
DS250HD (MB2W or MB2WL)
DS250TH (MB2W or MB2WL)
DS282
DS283 (MB2W or MB2WL)
DS283TH (MB2W or MB2WL)
Identifier
Operating Voltage Range
Model Name or Number
(Base model name or number in
parentheses.)
RPS-1000
24H
18.5–27.4 VDC
Compatibility ID
Head
Base
55000-350
45681-200
55000-250
45681-200
A
A
A
A
N/A
N/A
B
A
B
A
B
A
B
N/A
N/A
N/A
N/A
N/A
151153
# per Loop
24 / loop
24 / loop
30 / loop
30 / loop
30 / loop
30 / loop
30 / loop
30 / loop
30 / loop
30 / loop
30 / loop