Honeywell SILENT KNIGHT Farenhyt Series Installation And Operation Manual page 31

Intelligent power module
Table of Contents

Advertisement

Model RPS-1000 Installation Manual
151153
2. Configure the auxiliary power output through programming for Door Holder, Constant or
Resettable power.
Figure 3-16 Flexput Circuits Used as Auxiliary Power
3.5.6.1 Door Holder Power
Door holder is intended for fire door applications. When there are no alarms in the
system and the panel has AC power, door holder circuits have 24-volt power present
at their terminals. Any alarm will cause power to discontinue. Power will be re-applied
when the system is reset. If AC power is off for more than 15 seconds the auxiliary
door holder power will be discontinued to conserve the battery backup power. When
AC power is restored, power is immediately restored to the door holder circuits.
3.5.6.2 Constant Power
Use constant power for applications that require a constant auxiliary power source.
Power is always present at Constant circuits.
3.5.6.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors, and
conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt
power is always present at the terminals unless a system reset occurs. If a system
reset occurs, power is removed from the terminals for 30 seconds, then re-applied.
3.6
Conventional Relay Installation
RPS-1000 relay circuits are installed in exactly the same way as IFP-1000/IFP-
1000ECS main panel relay circuits. For ease of installation, the RPS-1000 output
terminals use the same numbering scheme as IFP-1000/IFP-1000ECS terminals.
Refer to the IFP-1000 Installation Manual (P/N 151139) or IFP-1000ECS Installation
Manual (PN 151460) for information on installing conventional relays.