Download Print this page

C-TEC EN54-13 Quick Start Manual

Sounder pcb

Advertisement

Quick Links

BF354
It is assumed this product will be installed by a technically competent person who is fully conversant with
the full Installation & Maintenance Manual for the CFP range of fire alarm panels.
Function
The EN54-13 Sounder PCB (shown right) provides two sounder circuits
for the CFP fire alarm panel that are fully compliant with EN54-13
(Compatibility Assessment of System Components).
Each sounder circuit has to be fitted with an Active end-of-line Device
(EOLD).
Items Supplied
1 x EN54-13 Sounder PCB (Part No. BF354) – shown right (above)
2 x Active EOLD (Part No. BF355) – shown right (below)
1 x 2-way polarised power supply loom
1 x 10K resistor
2 x retaining screws
Installation
Note the Sounder PCB has to be mounted inside the CFP enclosure.
Always remember to power down the system before fitting the Sounder PCB.
Step 1.
Isolate Mains supply to the CFP panel and disconnect the panel's battery back-up supply.
Step 2.
Remove the Main Control PCB from the CFP panel (note that the connection cable needs to
be disconnected from PL1 on the Power Supply PCB). See Fig.1.
Step 3.
Locate the two mounting slots provided in the base of the CFP panel, then slide the Sounder
PCB downwards into position and secure with two retaining screws (provided). See Fig.1.
Step 4.
Wire the 2-way polarised loom (supplied) from PL1 on the Sounder PCB to PL2 on the
Power Supply PCB. See Fig. 1.
Fig. 1 – Location of Panel's Base PCBs and Removal Details
Document No. DFU3540000 Rev 2
EN54-13 Sounder PCB
Errors and omissions excepted
Page 1 of 2

Advertisement

loading

Summary of Contents for C-TEC EN54-13

  • Page 1 Function The EN54-13 Sounder PCB (shown right) provides two sounder circuits for the CFP fire alarm panel that are fully compliant with EN54-13 (Compatibility Assessment of System Components). Each sounder circuit has to be fitted with an Active end-of-line Device (EOLD).
  • Page 2 Each circuit fused at 400mA hold current, 800mA max. trip current. Total Sounder Output Current: 2 x 400mA = 800mA. Maximum Number of Sounders: Dependant on type of sounder, see EN54-13 Model. Page 2 of 2 Errors and omissions excepted Document No. DFU3540000 Rev 2...

This manual is also suitable for:

Bf354