Output Features; Derating Curve - Honeywell CD3000M User Manual

Thyristor unit from 125a to 700a
Table of Contents

Advertisement

Honeywell

2.3 Output features

Current
Voltage
Ripetitive peak
range
reverse voltage
(A)
(V)
(480V)
1 2 5
2 4 ÷ 6 0 0
1 2 0 0
1 5 0
2 4 ÷ 6 0 0
1 2 0 0
2 0 0
2 4 ÷ 6 0 0
1 2 0 0
3 0 0
2 4 ÷ 6 0 0
1 2 0 0
4 0 0
2 4 ÷ 6 0 0
1 2 0 0
5 0 0
2 4 ÷ 6 0 0
1 2 0 0
6 0 0
2 4 ÷ 6 0 0
1 2 0 0
7 0 0
2 4 ÷ 6 0 0
1 2 0 0

2.4 Derating curve

I
= I
K
MAX
1
0.8
0.6
0.4
0.2
0
2.5 Fans
The thyristor units are equiped with a fan. The fan supply must be protected with a fuse.
Fan voltage supply is standard 230VAC ± 15% 50/60Hz or optional 110VAC ± 15% 50/60Hz.
The power consumption is given in the table below.
Size
125A up to 200A
300A up to 600A
700A
www.honeywell.com/imc
CD3000M-1PH from 125A to 700A
Latching
current
(600V)
(mAeff)
1 6 0 0
4 5 0
1 6 0 0
4 5 0
1 6 0 0
3 0 0
1 6 0 0
3 0 0
1 6 0 0
2 0 0
1 6 0 0
2 0 0
1 6 0 0
1 0 0 0
1 6 0 0
1 0 0 0
x K
NOM
45
55
65
Number of fans
One Fan - 14W
One Fan - 14W
Two Fans - 30W
Max peak
Leakage
one cycle
current
(10msec.) (A)
(mAeff)
1 5 4 0
1 5
2 0 0 0
1 5
4 8 0 0
1 5
5 2 5 0
1 5
7 8 0 0
1 5
8 0 0 0
1 5
1 7 8 0 0
1 5
1 7 8 0 0
1 5
75
85
8
2
I
T value
Frequency
Power loss
thyristor
range
I=Inom
tp=10msec
(Hz)
1 1 3 0 0
4 7 ÷ 7 0
1 9 1 0 0
4 7 ÷ 7 0
1 0 8 0 0 0
4 7 ÷ 7 0
1 2 8 0 0 0
4 7 ÷ 7 0
3 0 0 0 0 0
4 7 ÷ 7 0
3 0 6 0 0 0
4 7 ÷ 7 0
1 0 2 7 0 0 0
4 7 ÷ 7 0
1 0 2 7 0 0 0
4 7 ÷ 7 0
°C
U L
C
US
®
Number of fans
LISTED
One Fan - 14W
Two Fans - 30W
Two Fans - 30W
User's Manual
Isolation
Voltage
Vac
(W)
1 4 6
2 5 0 0
1 6 2
2 5 0 0
2 0 4
2 5 0 0
3 2 0
2 5 0 0
3 9 7
2 5 0 0
5 3 0
2 5 0 0
5 8 9
2 5 0 0
7 1 2
2 5 0 0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cd3000m-1ph

Table of Contents