Input Features - Honeywell CD3000M User Manual

Thyristor unit from 125a to 700a
Table of Contents

Advertisement

User's Manual
2. Technical specifications
2.1 General Features
Operating temperature
Voltage power supply
Input signal
Firing mode
Auxiliary voltage supply
Fan voltage supply
Fuses
Heather break alarm
Line Drop Voltage
Mounting
Protection

2.2 Input features

Input signal
SSR
Analog 0-10V
Analog 4-20mA
Potentiometer
10 K ohm
CD3000M-1PH from 125A to 700A
0÷45°C for higher temperature see derating curve
24 V minimum, 480V max and 600 V on request
SSR
4÷20 mA
0÷10V
potentiometer (10k ohm)
customer configurable with automatic zero/span calibration
One of these firing modes can be configured on line via serial port
Zero Crossing (ZC)
Single Cycle (SC)
Burst Firing (BF)
Soft Start + Burst Firing (S + BF)
Delayed Triggering + Burst Firing (DT + BF)
Phase Angle (PA)
230 à 200÷230V ±15%; 10 VA power consumption
460 à 300÷460V ±15%; 10 VA power consumption
230V ± 15 %;
110V ± 15 %; On request
Internal
Discrimination better than 20%. Circuit microprocessor based to
diagnose partial or total load failure and short circuit on Thyristors.
Latching alarm plus reset. Relay output 0.5A at 125VAC
Automatic compensation ± 15% of supply voltage with analog input
Bulk head mounting
IP20
Maximum current
drain
5mA constant current
-
-
Input
ON condition
Impedance
≥4V-max 30V
8200 ohm
100 ohm
8200 ohm
7
Honeywell
OFF condition
≤1V
www.honeywell.com/imc