02.12
05.01
Fuses that can be used: Sizes NH, D, DO with characteristic gL.
We recommend the following SIEMENS fuses that have no restrictions relating
to the characteristic power data of the NE modules.
Table 7-7
Assignment of fusible links to the NE modules
UI module
UI
5/10 kW
module
10/25 kW
Rated
16 A D01
25 A D02
voltage
Neoz./
Neoz./
400 VX
Order No.
Order No.
1)
5SE2316
5SE2325
Rated
16 A DII
25 A DII
voltage
Diazed/
Diazed/
500 VX
Order No.
Order No.
1)
5SB261
5SB261
Rated
16 A Size
25 A Size
voltage
00 LV
00 LV
500 VX
HRC/
HRC/
1)
Order No.
Order No.
3NA3805
3NA3810
Minimum
270 A
500 A
short-
circuit
2)
current
Fuses for North America
Designa-
AJT 17.5
AJT 25
tion
1)
Minimum
270 A
380 A
short-
circuit
2)
current
1) Tool to select the overcurrent protective devices, see Table 7-5
2) Minimum short–circuit current: Before connecting the machine to the line supply, the necessary minimum value must
be checked using a measurement corresponding to IEC 61557–3 and documented. If the minimum
short–circuit currents at the connection point are not reached, then there is a risk of fire in the case of a fault.
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
7.3 Overcurrent protective devices, transformers and main switch
UI module
I/R
I/R module
28/50 kW
module
36/47 kW
16/21 kW
–
35 A D02
Neoz./
Order No.
5SE2325
80 A DIV
35 A DIII
80 A DIV
Diazed/
Diazed/
Diazed/
Order No.
Order No.
Order No.
5SC211
5SB411
5SC211
80 A Size
35 A Size
80 A Size
00 LV
00 LV
00 LV
HRC/
HRC/
HRC/
Order No.
Order No.
Order No.
3NA3824
3NA3814
3NA3824
1600 A
700 A
1600 A
AJT 80
AJT 35
AJT 80
1100 A
600 A
1100 A
7 Line Supply Connection
I/R
I/R
module
module
55/71 kW
80/104 kW
–
–
–
–
–
125 A
160 A Size
Size 00
1 LV HRC/
LV HRC/
Order No.
Order No.
3NA3136
3NA3832
2800 A
3400 A
AJT 125
AJT 175
1800 A
2500 A
I/R module
120/156 KW
–
–
250 A Size 1
LV HRC/
Order No.
3NA3144
5800 A
AJT 250
3100 A
7-217