Removing The Liquid Pipe Thermistor - Hitachi FSXN Series Service Manual

Table of Contents

Advertisement

10 Servicing

10.14 Removing the liquid pipe thermistor

D A N G E R
Turn OFF all the power source switches.
1
Remove the front service cover as described in the procedure
2
Remove the cover of the electrical box as described in the procedures
(8-12)FSXN, see on page 295 and
3
Remove the cork tape -E- and pull out the thermistor -G- with the fixing plate -I- from the pipe -F-.
4
Remove the thermistor from the fixing plate -I-.
N O T E
When removing the thermistor of the liquid pipe, take care not to catch your hands or the thermistor on the
valve stay of the stop valve.
5
To fit the thermistor, carry out this procedure in reverse order.
N O T E
When fitting the thermistor, fix it with the end of the vinyl pipe -H- downward, to avoid entering water into
the pipe -F-.
Seal again the whole circumference of the pipe -F- with the cork tape -E-.
N O T E
The above procedure should be used to remove the other thermistors (Te, Tbg, Tg and Tchg).
Position of the thermistor in the RAS-12FSXN unit.
320
SMGB0065 rev. 1 - 12/2010
Removing the front service
Removing the electrical box for
cover, see on page 292.
Removing the electrical box for RAS-
RAS-(14-18)FSXN, see on page 295.

Advertisement

Table of Contents
loading

Table of Contents