Removing Thermistor For Liquid Pipe - Hitachi RPI-0.8FSG1 Service Manual

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

SERVICING
(2.1 Outdoor Unit)

2.1.12 Removing Thermistor for Liquid Pipe

Do not touch the electrical parts when the LED3 (Red) on the SNUBBER PCB (PCB5) or
the LED2 (Red) on the Inverter PCB (PCB3) is lit, since the voltage is higher than 50V.
(1) Remove the front service panel according to the item 2.1.2 "Removing Front Service Panel".
(2) Remove two (2) screws fixing the electrical box cover and remove the electrical box cover.
(3) Pull out the fixing plate for the thermistor from the pipe after detaching the CORK TAPE, and remove
the thermistor for the liquid pipe.
THM10
RAS-5FSG, 5FS3
8FSG, 8FS3
10FSG, 10FS3
THM10
RAS-24FSG1, 24FS5
30FSG1, 30FS5
2-28
TURN OFF all power source switches.
THM10
RAS-16FSG, 16FS3
20FSG, 20FS3
THM11
THM5
THM11
RAS-8FXG, 8FX3
10FXG, 10FX3
Thermistor
THM11
THM10
Thermistor
Holder
Seal completely
by cork tape.