5 Control system

5.1.3 Heat exchanger mode control

Heat recovery system: in accordance with the connected load of indoor units, the outdoor unit heat exchanger can
switch as indicated in the following table.
Heat pump system: in accordance with the operation mode of the indoor units, the outdoor unit heat exchanger can
switch as indicated in the following table.
N O T E
Outdoor unit heat exchanger mode at cooling: condenser (COND).
Outdoor unit heat exchanger mode at heating: evaporator (EVAP).
1
Heat exchanger mode:
COND: operating as condenser.
cond: avoid using the heat exchanger (under high pressure conditions).
EVAP: operating as evaporator.
evap: avoid using the heat exchanger (under low pressure conditions).
2
Expansion valve control method:
Pd: normally, completely open (the opening depends on the refrigerant cycle conditions). PI control is
carried out to reach the discharge pressure objective value when it decreases.
TdSH: PI control is carried out to reach the compressor TdSH objective value.
Heat exchanger SH: PI control is carried out to reach the heat exchanger SH objective value.
The number of outdoor unit: 1
Heat exchanger mode
Heat exchanger condition
RVR2
Reversing valve
RVR1
MV1
Expansion valve
MVB
The number of outdoor unit: 2
Heat exchanger mode
Heat exchanger condition
Reversing valve
Main outdoor
unit
Expansion valve
Heat exchanger condition
Reversing valve
Secondary
outdoor unit
Expansion valve
94
SMGB0065 rev. 1 - 12/2010
Cooling mode
Mainly cooling mode
COND
D1
COND
COND
OFF
OFF
ON
OFF
Pd
TdSH
TdSH
Cooling mode
Mainly cooling mode
COND
D1
COND
COND
RVR2
OFF
OFF
RVR1
ON
OFF
MV1
Pd
MVB
TdSH
COND
COND
RVR2
OFF
OFF
RVR1
ON
OFF
MV1
Pd
Pd
MVB
TdSH
Mainly heating mode
D1-1
D4
cond
EVAP
OFF
ON
OFF
OFF
Pd
Heat exchanger SH
Ps protection
Mainly heating mode
D2
D3
D4
COND
cond
EVAP
OFF
OFF
ON
OFF
OFF
OFF
Pd
Heat exchanger SH
TdSH
evap
EVAP
EVAP
ON
ON
ON
OFF
OFF
OFF
Completely closed
TdSH
Heating mode
Defrost mode
EVAP
DEF1
EVAP
COND
ON
OFF
OFF
ON
Completely open
TdSH
Heating mode
Defrost mode
DEF2
EVAP
With CH unit
Without CH unit
EVAP
COND/EVAP
ON
ON/OFF
OFF
OFF
Completely
Completely
open/Heat
exchanger SH
EVAP
COND/EVAP
ON
ON/OFF
OFF
OFF
Completely
Completely
open/Heat
exchanger SH
DEF1
COND
OFF
ON
closed
COND
OFF
ON
closed