CHAPTER 4: SOFTWARE
4.4.1

Description

4.4.2
Setting the
Baud Rate and
Parity
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
4.4

Chassis Mount Units

MM3 Motor Manager 3 chassis mount units no longer support automatic baud rate linking.
The default communication settings are 9600 baud, 8 data bits, one stop bit, no parity. It is
necessary to initially communicate with these settings and change them one at a time.
After each change the master must be changed to match the communication setting
change in the MM3 Motor Manager 3.
Assume your system communicates at 19200 baud and even
parity.
Use EnerVista MM3 Setup to establish communications with the
chassis mount MM3 Motor Manager 3 at 9600 baud and no parity.
Select the Communication > Set Slave Address menu item and
follow the on-screen instructions to store the communication
address of the MM3 Motor Manager 3.
When completed, select OK to exit.
CHASSIS MOUNT UNITS
4–15