FUNCTIONAL TESTS
7.2.2
Unbalance
Examples
7–4
For average currents less than the motor full load:
I
I
n
av
>
15% (alarm)
----------------
I
fl
where: I
= RMS current in any phase with maximum deviation from the average current,
n
I
= average of the phase currents, I
av
I
= phase B current, and I
b
c
EXAMPLE #1:
Find the percentage unbalance given the following information:
Value
Primary
Ia
73 A
Ib
100 A
Ic
100 A
We have I
given by:
av
I
I
+
a
b
I
=
------------------------
av
3
Since I
< I
, the following formula is used:
av
fl
% unbalance
Since the unbalance is greater than 15%, an unbalance alarm will occur if this condition
persists for longer than 5 seconds and auxiliary relay 1 will energize.
EXAMPLE #2:
Find the percentage of unbalance given the following information:
Value
Primary
Ia
100 A
Ib
80 A
Ic
150 A
We have I
given by:
av
I
I
+
a
b
I
=
------------------------
av
3
Since I
> I
, the following formula is used:
av
fl
% unbalance
=
Since unbalance is greater than 30%, a single phase trip will occur if this condition persists
for longer than 5 seconds and auxiliary relay 2 will energize.
30% trip
,
with
= motor full load current, I
fl
= phase C current.
Secondary (5 A)
3.65 A
5 A
5 A
I
+
73
100
100 A
c
+
+
=
------------------------------------------ -
3
I
I
73 91
n
av
×
100
-------------------
-------------------- -
=
=
I
100
fl
Secondary (5 A)
5 A
4 A
7.5 A
I
+
100
80
150 A
c
+
+
=
------------------------------------------ -
=
3
I
I
150 110
n
av
×
100
-------------------
--------------------------- -
=
I
110
av
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
CHAPTER 7: TESTING
I
I
I
+
+
a
b
c
I
=
------------------------
av
3
= phase A current,
a
273
-------- - A = 91 A
=
3
×
100
18%
=
330
-------- - A = 110 A
3
×
100
36.4 %
=
(EQ 7.2)
(EQ 7.3)
(EQ 7.4)
(EQ 7.5)
(EQ 7.6)