Lock Remote Read Programming - GE EST iO64 Technical Reference Manual

Table of Contents

Advertisement

Lock remote read programming

Lock remote read controls incoming TCP/IP communications when a
network card is installed and it is connected to a LAN or WAN. It
restricts Telnet, ping, and CU read requests at the panel so that
unwanted access to the panel is restricted, almost like a firewall.
Note:
Lock remote read is active when no one is logged onto the
panel or if someone with a level one password is logged on. When
you log onto the panel with a level two password, all
communication options are available and there are no restrictions.
To program lock remote read:
1.
Access the panel configuration options menu. See "Panel
configuration options."
2.
Choose Lock Rmt Read.
3.
Select either:
Yes: Telnet, ping, and CU read access to the panel are restricted.
No: Telnet is restricted, but ping and CU read access to the
panel are allowed.
4.
Program other panel configuration options or choose Save if
you're finished.
5.
Continue programming your system or press Menu to exit menu
mode.
EST iO64 and iO500 Technical Reference Manual
Chapter 3: Programming
Panel Configuration
MSK
255.255.255.000
GWY
000.000.000.000
Lock Rmt Read
Yes<>
Panel Configuration
GWY
000.000.000.000
Lock Rmt Read
Yes<>
Save
145

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Est io500